Daikin Enfinity CCW Installation And Maintenance Manual page 24

Horizontal water source heat pumps
Table of Contents

Advertisement

Unit Size 042 (575/60/3)
The fan motor on unit size 042 for voltage 575/60/3 has
a five-position terminal block and is factory wired for
high speed
(Figure
23). Low speed can be achieved by
interchanging black terminal (3) with red terminal (5) and
the black and blue terminals (3 & 4) receive a jumper as
shown in
Figure
24.
Figure 23: Size 042 (575/60/3) factory wired for high speed
GRN
FAN MOTOR
Figure 24: Size 042 (575/60/3) low speed
GRN
FAN MOTOR
Unit Size 048 (208-230/60/1 and 208-
230/60/3)
The fan motor on unit size 048 for voltages 208/230/60/1
and 208-230/60/3 have a four-position terminal block and
are factory wired for low speed
can be achieved by interchanging black terminal (3) with
red terminal (4).
Figure 25: Size 048 (208-230/60/1 and 208-230/60/3) factory
wired for low speed
GR / YE
FAN MOTOR
IM 1049-9
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
LINE
4 (BLU)
5 (RED)
HIGH SPEED
FACTORY WIRED
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
JUMPER LEAD
4 (BLU)
LINE
5 (RED)
LOW SPEED
(Figure
25). High speed
LINE
1 (YEL)
CAPACITOR
2 (BRN)
3 (BLK)
HIGH
4 (RED)
LOW
FACTORY
WIRED
Unit Size 048 (380/50/3, 460/60/3,
575/60/3)
The fan motor on unit size 048 for voltages 380/50/3,
460/60/3 and 575/60/3 have a five-position terminal block
and are factory wired for low speed
can be achieved by interchanging black terminal (3) with
red terminal (5) as shown in
Figure 26: Size 048 (380/50/3, 460/60/3, 575/60/3) factory
wired for low speed
GRN
FAN MOTOR
Figure 27: Size 048 (380/50/3, 460/60/3, 575/60/3) high
speed
GRN
FAN MOTOR
Unit Size 060 (208-230/60/1) & (208-
230/60/3)
The fan motor on unit size 060 in voltages 208-230/60/1
and 208-230/60/3 have a four-position terminal block and
are factory wired for high speed
can be achieved by interchanging black terminal (3) with
red terminal (4).
Figure 28: Sizes 060 (208-230/60/1) and (208-230/60/3)
GR / YE
FAN MOTOR
24
P
t
s
rior
o
tart
(Figure
26). High speed
Figure
27.
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
JUMPER LEAD
4 (BLU)
5 (RED)
LINE
LOW SPEED
FACTORY WIRED
1 (YEL)
LINE
CAPACITOR
2 (BRN)
3 (BLK)
LINE
4 (BLU)
5 (RED)
HIGH SPEED
(Figure
28). Low speed
LINE
1 (YEL)
CAPACITOR
2 (BRN)
HIGH
3 (BLK)
FACTORY
4 (RED)
WIRED
LOW
www.DaikinApplied.com
-
uP