Multi-Input/Output Device

Reference List of MIO Parameters

6
Reference List of MIO Parameters
List of Parameters, Legend
Char.: The column Char. shows characteristics or conditions applicable to this parameter.
These are:
OOS: Out of Service. The parameter can be written only if the target mode of the block is
"Out of Service".
S: Static. During each writing process an identified parameter of this type, the ST_REV
parameter is increased by one.
W: Writeable. The parameter can be modified by the user.
R: Readable. As all parameters can be read, this is not marked explicitly.
Transducer Block
Parameter
Breakaway Time Close ->
Open
Breakaway Time Close ->
Open Setpoint
Breakaway Time Open ->
Close
Breakaway Time Open ->
Close Setpoint
Counter Value
Cyclic Test Period
MIO Mode
Primary Value
PV_D Generation
RELATED_HW_CHANN
ELS
Sensor A Mode
54
Char.
Description
The last breakaway time measured from "closed" to
"open". This value is not stored on the device, i. e.,
this value is available after a power failure only after
opening and closing the valve once.
W
Reference value for the breakaway time from
S
"closed" to "open".
Range of values:
Reference value: 0 s ... 60 s
Maximum admissible deviation: 0 % ... 100 %
The last breakaway time from measured "open" to
"closed". This value is not stored on the device, i. e.,
this value is available after a power failure only after
opening and closing the valve once.
W
Reference value for the breakaway time from "open"
S
to "closed".
Range of values:
Reference value: 0 s ... 60 s
Maximum admissible deviation: 0 % ... 100 %
Counter value as float value with status information.
W
If the reference value of the valve is not modified for
S
this time, a cyclic function test is carried out.
Applicable if activated.
This parameter contains the MIO device mode
defined in the resource block parameter MIO Mode.
The valve position which is transferred to the function
block.
W
If the signals of the final position feedback are
S
evaluated, this parameter determines how to further
OOS
process the evaluated signals prior to transferring
them to the function block.
Contains the specific connected hardware inputs to a
transducer block.
TB1: hardware input 1, 2, 3
TB2: hardware input 4, 5, 6
TB3: hardware input 7, 8, 9
TB4: hardware input 10, 11, 12
W
In MIO binary mode: Enabling/disabling of the
OOS
hardware group 2 channels:
TB1:2, TB2:5, TB3:8, TB4:11