Transducer Block - Pepperl+Fuchs FieldConnex F2D0-MIO-Ex12.FF Series Manual

Multi-input/output device
Table of Contents

Advertisement

Multi-Input/Output Device
Troubleshooting and Diagnosis
5.4

Transducer Block

Diagnostic Messages
Problem
Parameter
Block Err.
Troubleshooting
Message
Cause
Block Configuration
The target mode is
Error
"Auto" or "Man" and the
Act. Fail Action
parameter is
"undefined".
Time monitoring or
stroke counter are ON
and the Sensor Usage
parameter is set to "No
position detection" or
"Use sensor values for
PV_D".
Time monitoring is ON
and one of the
reference values for
time monitoring is 0.
Input Failure
The status of the valve
position feedback to the
function block (Primary
Value) is BAD.
Output Failure
The combined error
signal of the errors is
displayed in the XD
Error parameter.
Maintenance Needed The Stroke Counter
Limit has been
exceeded.
Device Maintenance
The combined error
signal of the errors is
displayed in the Valve
Warning parameter.
Readback Check
Set if status of the
Failed
Primary Value
parameter is BAD.
Sensor Failure
In MIO sensor mode.
One or more sensor
inputs have a lead short
circuit or lead
breakage.
Out of Service
Block mode is out of
service.
Solution
Set the actuator fail
action parameter to the
drive mode "self-
closing" or "self-
opening".
See chapter 4.5.2
Set or have the Sensor
Usage parameter
automatically
determine one of the
options A ... D.
See chapter 4.5.3
Enter reference values
or determine them
automatically by
starting the setup
wizard.
See chapter 4.5.5
See section "Status
Values of Process
Parameters".
See XD Error
parameter.
Drive and valve need
maintenance since the
stroke number
specified for this was
exceeded. After
maintenance, increase
the stroke counter limit
or reset the counter
value in the Stroke
Counter parameter.
See Valve Warning
parameter.
Valve coupler mode:
Check wire connection.
Check wire connection.
Set block mode to auto.
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fieldconnex r8d0-mio-ex12.ff series

Table of Contents