Commissioning In Binary Input Mode; Commissioning In Frequency Or Counter Mode - Pepperl+Fuchs FieldConnex F2D0-MIO-Ex12.FF Series Manual

Multi-input/output device
Table of Contents

Advertisement

Multi-Input/Output Device
Installation and Commissioning
Parameterization Step 2 for Commissioning a Valve Coupler
Step
2.1
2.2
2.3
2.4
More Information
For more information on diagnostic messages and alarms, see chapter 4.5.12.
For a detailed list of the messages of the tranducer block parameters and for troubleshooting,
see chapter 5.4.
Tip
Test During Commissioning
During commissioning, you can perform function tests as follows: Set the DO function block to
the manual mode ("Man") and specify the reference value for the valve position directly via
OUT_D.
3.5

Commissioning in Binary Input Mode

In order to commission the MIO device in the binary input mode, parameterize the transducer
block parameters in the suggested order below.
Parameterization Steps for Commissioning a Binary Input
Step
1
2
3
4
5
6
7
3.6

Commissioning in Frequency or Counter Mode

In order to commission the MIO device in the frequency or counter mode, parameterize the
transducer block parameters in the suggested order below.
26
Description
Sensor signals for the value
position feedback.
Diagnostic settings for lead
interruption or short circuit
monitoring.
Diagnostic settings the cyclic
function test.
Setting the stroke counter and
limit value.
Description
Enable/disable hardware inputs 1,
4, 7, 10
Set sampling time hardware inputs
1, 4, 7, 10
Enable/disable hardware inputs 2,
5, 8, 11
Enable/disable hardware inputs 3,
6, 9, 12
Enable/disable lead fault
monitoring for all hardware inputs
Set fault state value for all
hardware inputs
Set information parameters of the
transducer blocks
Transducer Block
Parameters
Further Information
PV_D Generation
See chapter 4.5.3
Lead Fault Monitoring See chapter 4.5.8
Valve Monitoring
See chapter 4.5.6
Valve Monitoring
See chapter 4.5.7
Transducer Block
Parameters
Further Information
Mode
See chapter 4.6.2
Sensor On Time
See chapter 6
Sensor A Mode
See chapter 4.6.3
Sensor B Mode
See chapter 4.6.3
Lead Fault Monitoring See chapter 4.6.4
Sensor Fault State
See chapter 4.6.4
e. g., TAG_DESC
See chapter 6