Multi-Input/Output Device
Parameterization and Operation
Bit
3
4 ... 7
Group 2 Hardware Inputs
Bit
0
1
2
3
4
5
6
7
In the DI function block, the value of the FIELD_VAL_D parameter is assigned to the Primary
Value parameter, and from there, to the OUT_D parameter value. Thus, cyclic transmission of
the groups of sensor values to a control system is possible as well as their further use in a
function block application.
Because of the many inputs mapped to a single parameter, the status does not reflect the
status of a specific input any more. Failures, such as lead breakage or lead short circuit of the
sensor wires are no longer issued using the status. The status remains GOOD in all instances.
Only hardware failures of the MIO device are issued with the status BAD - Device Failure.
With the PV_FTIME parameter, you can determine for how long (in seconds) the final position
feedback sensor values have to be stable, before they are passed on from the FIELD_VSL_D
parameter to the Primary Value parameter.
Depending on the application used, sensor values can keep changing or influencing one
another. In this case, an inappropriate numeric value can result in the Primary Value parameter
not being updated at all. Therefore, Pepperl+Fuchs recommends setting the
PV_FTIME parameter to 0. If time monitoring is not necessary, Pepperl+Fuchs recommends
setting the Sensor Usage parameter to "Use sensor values for PV_D".
4.6.2

Enabling/Disabling Hardware Channels 1, 4, 7, 10

Use the Sensor Exe Mode parameter to individually enable or disable the channels 1, 4, 7, 10.
The Sensor On-Time parameter defines the time a specific hardware input is powered and
processed before the next hardware input is switched on.
Transducer Block
1
2
3
4
Description
Sensor value hardware channel 10
not used
Description
Sensor value hardware channel 2
Sensor value hardware channel 3
Sensor value hardware channel 5
Sensor value hardware channel 6
Sensor value hardware channel 8
Sensor value hardware channel 9
Sensor value hardware channel 11
Sensor value hardware channel 12
Hardware Channel
1
4
7
10
43