Standard Tags In Safety Routines (Tag Mapping) - Allen-Bradley GuardLogix 5580 Original Instructions Manual

Controller systems
Hide thumbs Also See for GuardLogix 5580:
Table of Contents

Advertisement

Chapter 5
Characteristics of Safety Tags, the Safety Task, and Safety Programs
46

Standard Tags in Safety Routines (Tag Mapping)

Controller-scoped standard tags can be mapped into safety tags, providing you
with a mechanism to synchronize standard and safety actions.
ATTENTION: When using standard data in a safety routine, you are responsible
for providing a more reliable means to make sure that the data is used in an
appropriate manner. The use of standard data in a safety tag does not make it
safety data. You must not directly control a safety output with standard tag
data.
This example illustrates how to qualify the standard data with safety data.
Figure 16 - Qualify Standard Data with Safety Data
MappedBooleanTag
LatchOneShot
ONS
Node30ComboModule:O.Pt03Data
Latch circuit to help prevent automatic restart if the standard
input (MappedTag) is failed in a 'stuck at 1' state.
Rockwell Automation Publication 1756-RM012B-EN-P - April 2018
Node30ComboModule:I.Pt07Data
Node30ComboModule:O.Pt03Data
Safety Input Qualifier for Mapped Tag
Safety Output

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Compact guardlogix 5380

Table of Contents