Commissioning
4.4 Frequently required parameters
Parameter
Explanation
p1900
Motor data identification and rotating measurement
0: Locked
1: Identify motor data and optimize the speed controller
2: Identify motor data (at standstill)
3: Optimize the speed controller (rotating in operation)
11: Ident. motor data and opt. speed controller, change to operation (not available with PM230 or PM250
Power Module)
12: Identify motor data (at standstill), change to operation (not available with PM230 or PM250 Power Mod-
ule)
p2030
Fieldbus interface protocol
selection
r2050
Words received via fieldbus (16 bit)
r2050[0]: PZD01 ... r2050[11]: PZD12
p2051
Words sent via fieldbus (16 bit)
p2051[0]: PZD01 ... p2051[16]: PZD17
p2080
Binector-connector converter, status word 1
p2080[0]: Bit 0 ... p2080[15]: Bit 15
r2090
PROFIdrive PZD1 receive bit-by-bit (control word 1)
r2090.00: Bit 0 ... r2090.15: Bit 15
p2200
Technology controller enable
p2201 ...
Technology controller fixed value 1 ... 15
p2215
p2220 ...
Technology controller fixed value selection bit 0 ... 3
p2223
r2224
Technology controller fixed value active
p2253
Technology controller setpoint 1
p2254
Technology controller setpoint 2
p2257
Technology controller ramp-up time
p2258
Technology controller ramp-down time
p2264
Technology controller actual value
p2265
Technology controller actual value filter time constant
p2267
Technology controller upper limit actual value
p2268
Technology controller lower limit actual value
p2271
Technology controller actual
value inversion (sensor type)
p2274
Technology controller differentiation time constant
p2280
Technology controller proportional gain
p2285
Technology controller integral time
p2293
Technology controller ramp-up/ramp-down time
48
The possible settings depend on the Control Unit:
0: No protocol
1: USS
2: Modbus RTU
3: PROFIBUS
1: Technology controller is enabled
0: No inversion
1: invert actual value signal (this should be set if the actual value decreas-
es with increasing motor speed)
Compact Operating Instructions, 01/2017, A5E38815802B AA
5: BacNet
7: PROFINET
8: P1
10: EtherNet/IP
CU230P-2 Control Units