Telegram 20:
STW1
ZSW1
PZD01/02
NSOLL_A
NIST_A_GLATT Smoothed actual speed value
Control word 1 (STW1), PZD receive word 1 (word: r2050[0], bits: r2090.00 ... r2090.15)
Bit
Meaning
0
0 = OFF1
0 → 1 = ON
1
0 = OFF2
1 = No OFF2
2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
3
0 = Inhibit operation
1 = Enable operation
4
0 = Disable RFG
1 = Do not disable RFG
5
0 = Stop RFG
1 = Enable RFG
6
0 = Inhibit setpoint
1 = Enable setpoint
7
0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still active (bit 0 = 1), the inverter switches to
8, 9
Reserved
10
0 = No control via PLC
1 = Control via PLC
11
1 = Direction reversal
12
Not used
13
1 = MOP up
14
1 = MOP down
15
Reserved
CU230P-2 Control Units
Compact Operating Instructions, 01/2017, A5E38815802B AA
Control word 1
Status word 1
Process data 16-bit
Speed setpoint
Explanation
The motor brakes with the ramp-down time p1121 of the ramp-function generator. The
inverter switches off the motor at standstill.
The inverter goes into the "ready" state. If, in addition bit 3 = 1, then the inverter
switches on the motor.
Switch off the motor immediately, the motor then coasts down to a standstill.
Precondition in order to be able to switch on the motor using bit 0 (ON command).
The motor brakes with the OFF3 ramp-down time p1135 down to standstill.
Precondition in order to be able to switch on the motor using bit 0 (ON command).
Switch off the motor immediately → motor coasts down to a standstill.
Precondition in order to be able to switch on the motor using bit 0 (ON command).
The inverter immediately sets its ramp-function generator output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator stops at the actual value.
The output of the ramp-function generator follows the setpoint.
The inverter brakes the motor with the ramp-down time p1121 of the ramp-function
generator.
Motor accelerates with the ramp-up time p1120 to the setpoint.
"closing lockout" state.
The inverter ignores the process data from the fieldbus.
Control via fieldbus, the inverter accepts the process data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the motorized potentiometer.
Reduce the setpoint saved in the motorized potentiometer.
Changes over between settings for different operation interfaces (command data sets).
4.3 Connecting the inverter to the fieldbus
IAIST_GLATT
Smoothed current actual
value
MIST_GLATT
Smoothed torque
PIST_GLATT
Smoothed active power
MELD_NAMUR Control word according to
the VIK-NAMUR definition