Advertisement

FC 300 Extended Relay Card Operating In-
structions

5.3 6-** Analog Outputs

5.3.1 6-7* Analog Output 3 MCB 113
Parameters for configuring the scaling and limits for analog output 3, Terminal X45/1 and X45/2. Analog outputs are current outputs: 0/4 – 20 mA.
Resolution on analog output is 11 bit.
6-70 Terminal X45/1 Output
Option:
[0]
No operation
[52]
MCO 305 0-20 mA
[53]
MCO 305 4-20 mA
[100]
Output frequency 0-20 mA
[101]
Reference 0-20 mA
[102]
Feedback
[103]
Motor current 0-20 mA
[104]
Torque rel to lim 0-20 mA
[105]
Torque rel to rated motor torque
0-20 mA
[106]
Power 0-20 mA
[107]
Speed 0-20 mA
[108]
Torque ref. 0-20 mA
[109]
Max Out Freq 0-20 mA
[130]
Output freq. 4-20 mA
[131]
Reference 4-20 mA
[132]
Feedback 4-20 mA
[133]
Motor cur. 4-20 mA
[134]
Torque % lim. 4-20 mA
[135]
Torque % nom 4-20 mA
[136]
Power 4-20 mA
Function:
Select the function of Terminal X45/1 as an analog current output.
When no signal on the analog output.
0 Hz = 0 mA; 100 Hz = 20 mA.
Par. 3-00 [Min - Max] 0% = 0 mA; 100% = 20 mA
Par. 3-00 [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA
Inv. Max. Current . Inverter max. current (160% current) is equal to
Value is taken from par. 16-37
20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
20
mA x 22 A
= 11.46
mA
A
38.4
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52
Max Scale is:
I VLT
x 100
Max
x 100
38.4
=
I Motor
22
Norm
The torque setting is related to setting in par. 4-16
The torque is related to the motor torque setting.
Motor Power [kW] .
Taken from par. 1-20
Taken from par. 3-03
Maximum Reference . 20 mA = value in par. 3-03 Maximum Reference
Torque reference related to 160% torque.
Max Output Frequency .
In relation to par. 4-19
0 Hz = 4 mA, 100 Hz = 20 mA
Par. 3-00 [Min-Max] 0% = 4 mA; 100% = 20 mA
Par. 3-00 [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Value is taken from par. 16-37
Inv. Max. Current . Inverter max. current (160% current) is equal to
20 mA.
Example: Inverter norm current (11 kW) = 24 A. 160 % = 38.4 A. Motor norm current = 22 A Read-
out 11.46 mA.
16
mA x 22 A
= 9.17
mA
A
38.4
In case the norm motor current is equal to 20 mA, the output setting of par. 6-52
Max Scale is:
I VLT
x 100
Max
x 100
38.4
=
I Motor
22
Norm
The torque setting is related to setting in par. 4-16
The torque setting is related to the motor torque setting.
Taken from par. 1-20
Motor Power [kW]
MI.33.G3.02 - VLT® is a registered Danfoss trademark
= 175 %
Torque Limit Motor Mode
= 175 %
Torque Limit Motor Mode .
5 Parameter Set-up
5
Terminal 42 Output
Terminal 42 Output
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcb 113

Table of Contents