FC 300 Extended Relay Card Operating In-
structions
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[84]
SL digital output E
[85]
SL digital output F
[120]
Local ref active
[121]
Remote ref active
[122]
No alarm
[123]
Start command activ
[124]
Running reverse
[125]
Drive in hand mode
[126]
Drive in auto mode
See par. 13-52
SL Controller Action . Output B is low on Smart Logic Action [33]. Output B is high
on Smart Logic Action [39].
See par. 13-52
SL Controller Action . Output C is low on Smart Logic Action [34]. Output C is high
on Smart Logic Action [40].
SL Controller Action . Output D is low on Smart Logic Action [35]. Output D is high
See par. 13-52
on Smart Logic Action [41]
See par. 13-52
SL Controller Action . Output E is low on Smart Logic Action [36]. Output E is high
on Smart Logic Action [42].
SL Controller Action . Output F is low on Smart Logic Action [37]. Output F is high
See par. 13-52
on Smart Logic Action [43].
Output is high when par. 3-13
Reference Site = [2] Local or when par. 3-13 Reference Site = [0]
Linked to hand auto at the same time as the LCP is in Hand on mode.
Reference
Reference site set in par. 3-13
Site
Reference site: Local par. 3-13
Reference
Site [2]
Reference site: Remote par. 3-13
ence Site [1]
Reference site: Linked to Hand/ Auto
Hand
Hand -> off
Auto -> off
Auto
Output is high when par. 3-13
Reference Site = Remote [1] or Linked to hand/auto [0] while the
LCP is in [Auto on] mode. See above.
Output is high when no alarm is present.
Output is high when the Start command high (i.e. via digital input, bus connection or [Hand on] or
[Auto on]), and a Stop has been last command.
Output is high when the frequency converter is running counter clockwise (the logical product of
the status bits 'running' AND 'reverse').
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Hand on]).
Output is high when the frequency converter is in 'Auto' mode (as indicated by LED on above [Auto
On]).
MI.33.G3.02 - VLT® is a registered Danfoss trademark
Local reference
active [120]
1
Refer-
0
1
1
0
0
5 Parameter Set-up
5
Remote reference
active [121]
0
1
0
0
0
1
23