5 Parameter Set-up
5-41 On Delay, Relay
Enter the delay of the relay cut-in time. See par. 5-40
Array [9]
0.01s*
[0.01 - 600.00 s ]
5
5-42 Off Delay, Relay
Enter the delay of the relay cut-out time. See par. 5-40
Array [8]
0.01s*
[0.01 - 600.00 s.]
24
Function Relay .
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 6 [5], Relay
Selected
Event
Relay
output
On Delay
P 5-41
Selected
Event
Relay
output
On Delay
P 5-41
Function Relay .
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay 6 [5], Relay 6 [5], Relay
Selected
Event
Relay
output
On Delay
P 5-41
If the Selected Event condition changes before the on- or off delay timer expires, the relay output
is unaffected.
MI.33.G3.02 - VLT® is a registered Danfoss trademark
FC 300 Extended Relay Card Operating In-
7 [6], Relay 8 [7], Relay 9 [8])
O Delay
P 5-42
7 [6], Relay 8 [7], Relay 9 [8])
O Delay
P 5-42
structions