5 Parameter Set-up
5.2.2 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. 5-01
cannot be adjusted while the motor is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready / remote control
[4]
Enable / no warning
[5]
VLT running
5
[6]
Running / no warning
[7]
Run in range / no warning
[8]
Run on reference / no warning
[9]
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedback range
[19]
Below feedback low
[20]
Above feedback high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal warning
[24]
Ready, no over-/ under voltage
[25]
Reverse
[26]
Bus OK
[27]
Torque limit and stop
[28]
Brake, no brake warning
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
18
Terminal 27 Mode , and set the I/O function for terminal 29 in par. 5-02 Terminal 29 Mode . These parameters
Default for all digital outputs and relay outputs
The control card is ready. E.g.: Feedback from a drive where the control is supplied by an external
24 V (MCB 107) and the main power to drive is not detected.
The frequency converter is ready for operation and applies a supply signal on the control board.
The frequency converter is ready for operation and is in Auto On mode.
Ready for operation. No start or stop command is been given (start/disable). No warnings are active.
Motor is running and shaft torque present.
Output speed is higher than the speed set in par. 1-81
motor is running and there are no warnings.
Motor is running within the programmed current and speed ranges set in par. 4-50
Low to par. 4-53 Warning Speed High . There are no warnings.
Motor runs at reference speed. No warnings.
An alarm activates the output. There are no warnings.
An alarm or a warning activates the output.
The torque limit set in par. 4-16
Mode has been exceeded.
The motor current is outside the range set in par. 4-18
Motor current is lower than set in par. 4-50
Motor current is higher than set in par. 4-51
Output frequency is outside the frequency range set in par. 4-52
Warning Speed High .
par. 4-53
Output speed is lower than the setting in par. 4-52
Output speed is higher than the setting in par. 4-53
Feedback is outside the range set in par. 4-56
back High .
Feedback is below the limit set in par. 4-56
Feedback is above the limit set in par. 4-57
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency
converter, the brake resistor, or the thermistor.
Frequency converter is ready for operation and there is no over-temperature warning.
Frequency converter is ready for operation and is in Auto On mode. There is no over-temperature
warning.
Frequency converter is ready for operation and the mains voltage is within the specified voltage
range (see
General Specifications section in the Designn Guide).
Reversing. Logic '1' when CW rotation of the motor. Logic '0' when CCW rotation of the motor. If
the motor is not rotating the output will follow the reference.
Active communication (no time-out) via the serial communication port.
Use in performing a coasting stop and in torque limit condition. If the frequency converter has
received a stop signal and is at the torque limit, the signal is Logic '0'.
Brake is active and there are no warnings.
Brake is ready for operation and there are no faults.
Output is Logic '1' when the brake IGBT is short-circuited. Use this function to protect the frequency
converter if there is a fault on the brake modules. Use the output/relay to cut out the main voltage
from the frequency converter.
MI.33.G3.02 - VLT® is a registered Danfoss trademark
FC 300 Extended Relay Card Operating In-
Min Speed for Function at Stop [RPM] . The
Torque Limit Motor Mode or par. 4-17 Torque Limit Generator
Current Limit .
Warning Current Low .
Warning Current High .
Warning Speed Low .
Warning Speed High .
Warning Feedback Low and par. 4-57 Warning Feed-
Warning Feedback Low .
Warning Feedback High .
structions