Advertisement

5 Parameter Set-up
[83]
SL Digital Output D
[84]
SL Digital Output E
[85]
SL Digital Output F
[120]
Local reference active
5
[121]
Remote reference active
[122]
No alarm
[123]
Start command active
[124]
Running reverse
[125]
Drive in hand mode
[126]
Drive in auto mode
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105), Relay
8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
[0] *
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive rdy/rem ctrl
[4]
Enable / no warning
[5]
Running
[6]
Running / no warning
20
See par. 13-52
SL Controller Action . The input will go high whenever the Smart Logic Action [41]
Set dig. out. A high is executed. The input will go low whenever the Smart Logic Action [35] Set
dig. out. A low is executed.
SL Controller Action . The input will go high whenever the Smart Logic Action [42]
See par. 13-52
Set dig. out. A high is executed. The input will go low whenever the Smart Logic Action [36] Set
dig. out. A low is executed.
SL Controller Action . The input will go high whenever the Smart Logic Action [43]
See par. 13-52
Set dig. out. A high is executed. The input will go low whenever the Smart Logic Action [37] Set
dig. out. A low is executed.
Reference Site = [2] Local or when par. 3-13 Reference Site = [0]
Output is high when par. 3-13
Linked to hand auto at the same time as the LCP is in Hand on mode.
Reference site set in par. 3-13
Reference
Site
Reference site: Local par. 3-13
Reference
Site [2]
Reference site: Remote par. 3-13
ence Site [1]
Reference site: Linked to Hand/ Auto
Hand
Hand -> off
Auto -> off
Auto
Output is high when par. 3-13
Reference Site = Remote [1] or Linked to hand/auto [0] while the
LCP is in [Auto on] mode. See above.
Output is high when no alarm is present.
Output is high when there is an active Start command (i.e. via digital input bus connection or [Hand
on] or [Auto on]), and no Stop or Start command is active.
Output is high when the frequency converter is running counter clockwise (the logical product of
the status bits 'running' AND 'reverse').
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Hand on]).
Output is high when the frequency converter is in Hand on mode (as indicated by the LED light
above [Auto on]).
Function:
All digital and relay outputs are default set to "No Operation".
The control card is ready. E.g.: Feedback from a drive where the control is supplied by an external
24 V (MCB 107) and the main power to drive is not detected.
Drive is ready to operate. Mains and control supplies are OK.
The frequency converter is ready for operation and is in Auto On mode
Ready for operation. No start or stop commands have been applied (start/disable). No warnings are
active.
Motor is running, and shaft torque present.
Output speed is higher than the speed set in par. 1-81
Speed for Function at Stop [RPM]. The motor is running and no warnings.
MI.33.G3.02 - VLT® is a registered Danfoss trademark
FC 300 Extended Relay Card Operating In-
Local reference
active [120]
1
Refer-
0
1
1
0
0
Min Speed for Function at Stop [RPM] Min
structions
Remote reference
active [121]
0
1
0
0
0
1