Table 6- 9
Derating of the output current as a function of the line voltage, 3 AC 500 V ... 690 V
Power Module
6SL3310-1PG33-7AA0 368 A / 340 A
6SL3310-1PG34-0AA0 400 A / 393 A
6SL3310-1PG34-5AA0 453 A / 430 A
6SL3310-1PG35-2AA0 516 A / 480 A
6SL3310-1PG35-8AA0 581 A / 535 A
6SL3310-1PG36-5AA0 654 A / 595 A
6SL3310-1PG37-2AA0 725 A / 665 A
6.3.4

Derating of the output current as a function of the pulse frequency

With the factory setting, the drive starts with a 4 kHz pulse frequency, and under load,
automatically reduces the pulse frequency step-by-step to the frequencies required. When
the load decreases, the pulse frequency is increased automatically up to 4 kHz.
The values of the rated current apply to a pulse frequency of 2 kHz at 40° C ambient
temperature and are reached at any time by the automatic adaptation of the output pulse
frequency.
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
Rated output current I
at
N
500 V/690 V
500 V
575 V
100%
97.0%
100%
99.3%
100%
98.0%
100%
97.3%
100 %
96.9%
100 %
96.5 %
100 %
96.7%
Technical specifications
6.3 Derating data
600 V
660 V
95.9%
93.5%
99.0%
98.6%
97.3%
95.8%
96.3 %
94.2%
95.4%
93.3 %
95.3%
92.4%
95.6%
93.0 %
690 V
92.6%
98.3%
95.0%
93.1%
92.1 %
91.0%
91.7 %