Ambient conditions
Ambient temperature
Relative humidity
(no condensation)
Corresponds to class
Environmental class /
harmful chemical substances
Organic/biological influences 1B1 acc. to EN 60721-3-1
Pollution degree
Installation altitude
Mechanical strength
Vibrational load
- Displacement
- Acceleration
Shock load
- Displacement
- Acceleration
Deviations from the defined classes are shown in
maximum sound pressure level, ascertained in the IP20 cabinet
1)
Standard construction: Devices installed in the control cabinet with installation in conformance with EMC regulations,
2)
line reactor uk = 2%, shielded motor cable (e.g. Protoflex EMC) with max. 100 m cable length,
line harmonics according to EN 61000-2-4: Class 2, THD(U) total = 8% for typical line conditions (RSC > 30 ... 50);
THD(I) total: typically 30 ... 45 % (15 < RSC < 50)
in transport packaging
3)
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
During storage
3)
-25° ... +55° C
5 to 95%
1K4 acc. to EN 60721-3-1
1C2 acc. to EN 60721-3-1
2 according to EN 61800-5-1
up to 1000 m above sea level without derating,
> 1000 m above sea level with derating (see Chapter Derating as a function of the installa-
tion altitude (Page 83))
During storage
3)
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
italics
.
During transport
3)
-25 ... +70 °C
–40 °C
from
for 24 hours
5 ... 95% at 40° C
2K3 acc. to EN 60721-3-2
2C2 acc. to EN 60721-3-2
2B1 acc. to EN 60721-3-2
During transport
3)
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g at 9 ... 200 Hz
Fc test according to
EN 60068-2-6
±1.5 mm for 5 ... 9 Hz
0.5 g for 9 ... 200 Hz
Technical specifications
6.1 General technical data
During operation
0° ... +40° C
up to + 50° C with derating
5 ... 95%
3K3 acc. to EN 60721-3-3
3C2 acc. to EN 60721-3-3
3B1 acc. to EN 60721-3-3
During operation
Fc test according to
EN 60068-2-6
0.075 mm for 10 ... 58 Hz
9.81 ma/s² (1 x g) at > 58 ...
200 Hz
Test according to EN 60068-
2-27 (EA shock type)
49 ma/s² (5 x g)/30 ms
147 m/s² (15 x g)/11 ms
67