Siemens SINAMICS G120P PM330 Installation Manuals page 80

Power modules
Table of Contents

Advertisement

Technical specifications
6.2 Specific technical data
Article No.
Recommended cable cross-section for 500 V
- DC link infeed (2/3 converter power)
Recommended cable cross-section for 690 V
- DC link infeed (2/3 converter power)
Tightening torque for line, motor, DC link, and
ground cable
Dimensions: Width x height x depth (mm)
Weight
Minimum control cabinet size for installation of the
Power Module (width x height x depth)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
1)
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, the rupture time for the fuses increases, which may result in
consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
2)
80
6SL3310-
1PG35-2AA0
2 x 150 mm
2 x 150 mm
50 Nm / 443 lbf in
548 x 1695 x 393
162 kg
2
2
800 mm x 2000 mm x 600 mm
Hardware Installation Manual, 10/2016, A5E32844552B AD
Power Module PM330