6.2 Specific technical data
Article no.
Recommended cable cross-section for 480 V
- DC link infeed (2/3 converter power)
- Braking Module
4)
Tightening torque for line, motor, DC link, and
ground cable
Dimensions: Width x height x depth (mm)
Weight
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
1)
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, the tripping time for the fuses increases, which may result in
consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
2)
The motor cables must be evenly distributed on both connection chambers.
3)
For connection of the Braking Module with rated power of 50 kW, P
4)
76
6SL3310-
1PE38-4AA0
3 x 120 mm
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
235 kg
1PE38-8AA0
3 x 150 mm
2
2
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
250 kg
power of 200 kW.
20
Hardware Installation Manual, 10/2016, A5E32844552B AD
1PE41-0AA0
3 x 185 mm
2
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
250 kg
Power Module PM330