PowerFlex 700 Adjustable Frequency AC Drive – Frames 7...10
52

I/O Wiring Examples

Input/Output
Connection Example
Potentiometer Unipolar
(1)
Speed Reference
10k Ohm Pot. Recommended
(2k Ohm Minimum)
Joystick Bipolar Speed
(1)
Reference
±10V Input
Analog Input Bipolar
Speed Reference
±10V Input
Analog Voltage Input
Unipolar Speed
Reference
0 to +10V Input
Analog Current Input
Unipolar Speed
Reference
0-20 mA Input
Analog Input, PTC
PTC OT set > 5V
1.8k
PTC OT cleared < 4V
PTC
PTC Short < 0.2V
(2)
HW PTC Input
1.8k
PTC OT set > 5V
PTC
PTC OT cleared < 4V
PTC Short < 0.2V
(1) Refer to the Attention statement on
(2) A PTC (Positive Temperature Coefficient) device (motor thermistor) embedded in the motor windings, can be monitored by the drive
for motor thermal protection.
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
Required Parameter Changes
• Adjust Scaling:
• View Results:
3
4
5
22
• Set Direction Mode:
• Adjust Scaling:
3
5
21
• View Results:
22
• Set Direction Mode:
• Adjust Scaling:
3
Common
+
4
• View Results:
• Configure Input with parameter 320
• Adjust Scaling:
3
Common
• View results:
4
+
• Configure Input for Current:
3
19
Common
• Adjust Scaling:
4
20
+
• View results:
• Set Fault Config 1:
Ferrite
Bead
1
• Set Alarm Config 1:
2
• View Status Drive Alarm 1:
5
3.32k
22
Ohm
• Set Fault Config 1:
23
• Set Alarm Config 1:
Ferrite
10
Bead
• View Status: Drive Alarm 1:
page 49
for important bipolar wiring information.
Parameters 91/92 and 325/326
Parameter 002
Parameter 190 = "1, Bipolar"
Parameters 91/92 and 325/326
Parameter 002
Parameter 190 = "1, Bipolar"
Parameters 91/92 and 325/326
Parameter 002
Parameters 91/92 and 325/326
Parameter 002
Parameter 320 and add jumper at
appropriate terminals
Parameters 91/92 and 325/326
Parameter 002
Parameter 238, bit 7 = "Enabled"
Parameter 259, bit 11 = "Enabled"
Parameter 211, bit 11 = "True"
Parameter 238, bit 13 = "Enabled"
Parameter 259, bit 18 = "Enabled"
Parameter 211, bit 18 = "True"