neuro 102 EX
Enhanced Universal Single Loop
Process Controller
CONFIGURATION PARAMETERS : PAGE 12
Parameters
Settings
Parameters
(Default Value)
Pulse Time
Control Output
Relay
(OP1) Type
ON Time
SSR
0 - 20mA
Cool Hysteresis
4 - 20mA
0 - 5 V
Cool Pulse Time
0 - 10 V
(Default : Relay)
Cool ON Time
Control Action
On-Off
Pulse
Heat Power Low
PID
(Default : PID)
Heat Power High
Control Logic
Reverse
Direct
Cool Power Low
(Default : Reverse)
Input Type
Refer Table 1
Cool Power High
(Default : Type K)
PV Resolution
Refer Table 1
(Default : 1)
SUPERVISORY PARAMETERS : PAGE 13
PV Units
°C
Parameters
°F
Self-Tune Command
(Default : C)
°
PV Range Low
-19999 to PV Range High
(Default : 0)
Overshoot Inhibit
PV Range High
PV Range Low to 9999
(Default : 1000)
Setpoint Low Limit
Min. Range for the
Overshoot Inhibit
selected Input Type to
Factor
Setpoint High Limit
(Default : -200.0)
Setpoint High Limit
Setpoint Low Limit to
Auxiliary Setpoint
Max. Range for the
selected Input Type
(Default : 1376.0)
Offset for PV
-199 to 999 or
-1999.9 to 9999.9
Recorder
(Default : 0)
(Retransmission)
Output
Digital Filter Time
0.5 to 60.0 Seconds
Constant
(in steps of 0.5 Seconds)
(Default : 2.0 Sec.)
SP Adjustment on
Lower Readout
Sensor Break Output
Power
0 to 100 or -100.0 to 100.0
(Default : 0)
SP Adjustment
on Operator Page
CONTROL PARAMETERS : PAGE 10
Settings
Parameters
(Default Value)
Manual Mode
Proportional Band
0.1 to 999.9 Units
(Default : 50 units)
Integral Time
0 to 3600 Seconds
(Default : 100 Sec.)
Alarm SP Adjustment
on Operator Page
Derivative Time
0 to 600 Seconds
(Default : 16 Sec.)
Cycle Time
0.5 to 100.0 Seconds
Standby Mode
(in steps of 0.5 secs.)
(Default : 10.0 Sec.)
Relative Cool Gain
0.1 to 10.0
(Default : 1.0)
Profile Abort Command
on Operator Page
Cool Cycle Time
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 sec.)
Hysteresis
1 to 999 or 0.1 to 999.9
(Default : 0.2)
This brief manual is primarily meant for quick reference to wiring
connections and parameter searching. For more details on
operation and application; please log on to www.ppiindia.net
Settings
Settings
Parameters
(Default Value)
(Default Value)
Pulse ON Time
Baud Rate
4800
to 120.0 Seconds
(Default : 2.0 sec.)
9600
0.1 to Value set
for Pulse Time
19200
(Default : 1.0)
38400
1 to 999 or 0.1 to 999.9
57600
(Default : 2)
(Default : 9.6)
Cool ON Time
to 120.0 Seconds
Communication Parity
None
(Default : 2.0)
Even
0.1 to Value set for
Cool Pulse Time
Odd
(Default : 1.0)
(Default : Even)
0 to Power High
Controller ID Number
(Default : 0)
1 to 127
(Default : 1)
Power Low to 100%
Communication
(Default : 100.0)
No
Write Enable
Yes
0 to Cool Power High
(Default : No)
(Default : 0)
Cool Power Low to 100%
OP2 & OP3,OP4,OP5 FUNCTION PARAMETERS : PAGE 15
(Default : 100)
Settings
Parameters
(Default Value)
Output-2 Function
None
Selection
End Of
Settings
Profile
(Default Value)
Cool Control
No
(Default : None)
Yes
Output-2 Type
Relay
(Default : No)
SSR
Disable
0 - 20mA
Enable
4 - 20mA
(Default : Disable)
0 - 5 V
1.0 to 2.0
(Default : 1.0)
0 - 10 V
(Default : Relay)
OP2 Event Status
Disable
ON
Enable
OFF
(Default : Disable)
(Default : ON)
Disable
OP2 Event Time
0 to 9999
(Default : 0)
Enable
(Default : Disable)
OP2 Event Time Units
Seconds
Disable
Minutes
Enable
Hours
(Default : Enable)
(Default : Seconds)
Disable
Output-3 Function
None
Selection
Enable
Alarm
(Default : Enable)
End of
Profile
Disable
(Default : Alarm)
Enable
Alarm-1 Logic
Normal
(Default : Disable)
Reverse
Disable
(Default : Normal)
OP3 Event Status
Enable
ON
(Default : Disable)
OFF
Disable
(Default : ON)
OP3 Event Time
Enable
0 to 9999
(Default : 0)
(Default : Disable)
OP3 Event Time Units
Seconds
Disable
Minutes
Enable
(Default : Disable)
Hours
(Default : Seconds)
Operation Manual
Settings
PROFILE CONFIGURATION PARAMETERS : PAGE 16
Parameters
(Default Value)
Parameters
Alarm-2 Logic
Normal
Profile mode selection
Reverse
(Default : Normal)
Recorder
Process
Transmission Type
Value
Number of Segments
Setpoint
(Default : Process Value)
Number of Repeats
Recorder Output Type
0 to 20mA
4 to 20mA
Common Holdback
0 to 5 Volts
0 to 10 Volts
(Default : 0 to 20mA)
Output Off
Recorder Low
Min. to Max. Range
Specified for the
Selected Input Type
(Default : -199)
Recorder High
Min. to Max. Range
Power Fail Strategy
Specified for the
Selected Input Type
(Default : 1376)
ALARM PARAMETERS : PAGE 11
Settings
PROFILE SETTING PARAMETERS : PAGE 14
Parameters
(Default Value)
Parameters
Alarm-1 Type
None
Segment Number
Process
Low
Process
High
Target Setpoint
Deviation
Band
Window
Band
Time Interval
(Default : None)
Alarm-1 Setpoint
Min. to Max. Range
specified for the
selected Input Type
Holdback Type
(Default : Min or Max Range)
Alarm-1 Deviation Band
-999 to 999
or -999.9 to 999.9
(Default : 5.0)
Alarm-1 Window Band
3 to 999 or 0.3 to 999.9
(Default : 5.0)
Holdback Value
Alarm-1 Hysteresis
1 to 999 or 0.1 to 999.9
(Default : 2)
Alarm-1 Inhibit
No
PROFILE STATUS INFORMATION : PAGE 1
Yes
Lower Readout
(Default : Yes)
Prompt
Alarm-2 Type
None
Process
Low
Process
High
Deviation
Band
Window
Band
(Default : None)
Alarm-2 Setpoint
Min. to Max. Range
specified for the
selected Input Type
(Default : Min or Max Range)
Alarm-2 Deviation Band
-999 to 999 or
-999.9 to 999.9
(Default : 5.0)
Alarm-2 Window Band
3 to 999 or
0.3 to 999.9
(Default : 5.0)
Alarm-2 Hysteresis
1 to 999 or
0.1 to 999.9
(Default : 2.0)
Alarm-2 Inhibit
No
Yes
(Default : Yes)
ON-LINE ALTERATION PARAMETERS : PAGE 2
Settings
Effect on the running segment
Parameters
(Default Value)
Time Interval
RAMP:- Altering the time
Disable
interval shall immediately
affect the 'Ramp Rate' for the
Enable
current segment.
(Default : Disable)
SOAK:- Elapsed time so far is
ignored and the soak timer
1 to 16
starts counting down to 0 from
(Default : 16)
the altered time interval value.
1 to 9999
Holdback Type
The modified Holdback Band
(Default : 1)
Type is applied immediately on
the current segment.
No
Holdback Value
The modified Holdback Band
Value is applied immediately
Yes
on the current segment.
(Default : Yes)
No
USER LINEARISATION PARAMETERS : PAGE 33
Yes
Effect on the running segment
Parameters
(Default : No)
Code
0 to 9999
Abort
(Default : 0)
Continue
User Linearisation
Disable
(Default : Continue)
Enable
(Default : Disable)
Total Break
Settings
1 to 32
Points
(Default Value)
(Default : 2)
1 to 16
(Default : 1)
Break Point
Number
1 to 32
Min. to Max. Range
(Default : 1)
specified for the
selected Input Type
Actual Value for
(Default : -199)
Break Point
-1999 to 9999
(X co-ord)
(Default : Undefined)
0 to 9999 Minutes
(Default : 0)
Derived Value for
Break Point
None
-1999 to 9999
(Y co-ord)
(Default : Undefined)
Up
Down
Both
(Default : None)
1 to 999
(Default : 1)
Upper Readout
Information
Active Segment Number
Segment Type
Target Setpoint
Ramping Setpoint
Balance Time
Balance Repeats
TABLE- 1
Option
Range (Min. to Max.)
Resolution
0 to +960°C / +32 to +1760°F
J Type T/C
-200 to +1376°C / -328 to +2508°F
K Type T/C
-200 to +385°C / -328 to +725°F
T Type T/C
0 to +1770°C / +32 to +3218°F
R Type T/C
Fixed
0 to +1765°C / +32 to +3209°F
1°C / 1°F
S Type T/C
0 to +1825°C / +32 to +3218°F
B Type T/C
0 to +1300°C / +32 to +2372°F
N Type T/C
Reserved for customer specific
Thermocouple type not listed
above.
User settable
-199 to +600°C / -328 to +1112°F
1°C / 1°F
or
or
-199.9 to 600.0°C / -199.9 to 999.9°F
RTD Pt100
0.1°C / 0.1°F
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC
0 to 200mV DC
User settable
-1999 to +9999 units
1 / 0.1 / 0.01/
0.001 units
0 to 1.25V DC
0 to 5.0V DC
0 to 10.0V DC
1 to 5.0V DC