PPI neuro 102 EX Operation Manual

Enhanced universal single loop process controller

Advertisement

Quick Links

neuro 102 EX
Enhanced Universal Single Loop
Process Controller
CONFIGURATION PARAMETERS : PAGE 12
Parameters
Settings
Parameters
(Default Value)
Pulse Time
Control Output
Relay
(OP1) Type
ON Time
SSR
0 - 20mA
Cool Hysteresis
4 - 20mA
0 - 5 V
Cool Pulse Time
0 - 10 V
(Default : Relay)
Cool ON Time
Control Action
On-Off
Pulse
Heat Power Low
PID
(Default : PID)
Heat Power High
Control Logic
Reverse
Direct
Cool Power Low
(Default : Reverse)
Input Type
Refer Table 1
Cool Power High
(Default : Type K)
PV Resolution
Refer Table 1
(Default : 1)
SUPERVISORY PARAMETERS : PAGE 13
PV Units
°C
Parameters
°F
Self-Tune Command
(Default : C)
°
PV Range Low
-19999 to PV Range High
(Default : 0)
Overshoot Inhibit
PV Range High
PV Range Low to 9999
(Default : 1000)
Setpoint Low Limit
Min. Range for the
Overshoot Inhibit
selected Input Type to
Factor
Setpoint High Limit
(Default : -200.0)
Setpoint High Limit
Setpoint Low Limit to
Auxiliary Setpoint
Max. Range for the
selected Input Type
(Default : 1376.0)
Offset for PV
-199 to 999 or
-1999.9 to 9999.9
Recorder
(Default : 0)
(Retransmission)
Output
Digital Filter Time
0.5 to 60.0 Seconds
Constant
(in steps of 0.5 Seconds)
(Default : 2.0 Sec.)
SP Adjustment on
Lower Readout
Sensor Break Output
Power
0 to 100 or -100.0 to 100.0
(Default : 0)
SP Adjustment
on Operator Page
CONTROL PARAMETERS : PAGE 10
Settings
Parameters
(Default Value)
Manual Mode
Proportional Band
0.1 to 999.9 Units
(Default : 50 units)
Integral Time
0 to 3600 Seconds
(Default : 100 Sec.)
Alarm SP Adjustment
on Operator Page
Derivative Time
0 to 600 Seconds
(Default : 16 Sec.)
Cycle Time
0.5 to 100.0 Seconds
Standby Mode
(in steps of 0.5 secs.)
(Default : 10.0 Sec.)
Relative Cool Gain
0.1 to 10.0
(Default : 1.0)
Profile Abort Command
on Operator Page
Cool Cycle Time
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 sec.)
Hysteresis
1 to 999 or 0.1 to 999.9
(Default : 0.2)
This brief manual is primarily meant for quick reference to wiring
connections and parameter searching. For more details on
operation and application; please log on to www.ppiindia.net
Settings
Settings
Parameters
(Default Value)
(Default Value)
Pulse ON Time
Baud Rate
4800
to 120.0 Seconds
(Default : 2.0 sec.)
9600
0.1 to Value set
for Pulse Time
19200
(Default : 1.0)
38400
1 to 999 or 0.1 to 999.9
57600
(Default : 2)
(Default : 9.6)
Cool ON Time
to 120.0 Seconds
Communication Parity
None
(Default : 2.0)
Even
0.1 to Value set for
Cool Pulse Time
Odd
(Default : 1.0)
(Default : Even)
0 to Power High
Controller ID Number
(Default : 0)
1 to 127
(Default : 1)
Power Low to 100%
Communication
(Default : 100.0)
No
Write Enable
Yes
0 to Cool Power High
(Default : No)
(Default : 0)
Cool Power Low to 100%
OP2 & OP3,OP4,OP5 FUNCTION PARAMETERS : PAGE 15
(Default : 100)
Settings
Parameters
(Default Value)
Output-2 Function
None
Selection
End Of
Settings
Profile
(Default Value)
Cool Control
No
(Default : None)
Yes
Output-2 Type
Relay
(Default : No)
SSR
Disable
0 - 20mA
Enable
4 - 20mA
(Default : Disable)
0 - 5 V
1.0 to 2.0
(Default : 1.0)
0 - 10 V
(Default : Relay)
OP2 Event Status
Disable
ON
Enable
OFF
(Default : Disable)
(Default : ON)
Disable
OP2 Event Time
0 to 9999
(Default : 0)
Enable
(Default : Disable)
OP2 Event Time Units
Seconds
Disable
Minutes
Enable
Hours
(Default : Enable)
(Default : Seconds)
Disable
Output-3 Function
None
Selection
Enable
Alarm
(Default : Enable)
End of
Profile
Disable
(Default : Alarm)
Enable
Alarm-1 Logic
Normal
(Default : Disable)
Reverse
Disable
(Default : Normal)
OP3 Event Status
Enable
ON
(Default : Disable)
OFF
Disable
(Default : ON)
OP3 Event Time
Enable
0 to 9999
(Default : 0)
(Default : Disable)
OP3 Event Time Units
Seconds
Disable
Minutes
Enable
(Default : Disable)
Hours
(Default : Seconds)
Operation Manual
Settings
PROFILE CONFIGURATION PARAMETERS : PAGE 16
Parameters
(Default Value)
Parameters
Alarm-2 Logic
Normal
Profile mode selection
Reverse
(Default : Normal)
Recorder
Process
Transmission Type
Value
Number of Segments
Setpoint
(Default : Process Value)
Number of Repeats
Recorder Output Type
0 to 20mA
4 to 20mA
Common Holdback
0 to 5 Volts
0 to 10 Volts
(Default : 0 to 20mA)
Output Off
Recorder Low
Min. to Max. Range
Specified for the
Selected Input Type
(Default : -199)
Recorder High
Min. to Max. Range
Power Fail Strategy
Specified for the
Selected Input Type
(Default : 1376)
ALARM PARAMETERS : PAGE 11
Settings
PROFILE SETTING PARAMETERS : PAGE 14
Parameters
(Default Value)
Parameters
Alarm-1 Type
None
Segment Number
Process
Low
Process
High
Target Setpoint
Deviation
Band
Window
Band
Time Interval
(Default : None)
Alarm-1 Setpoint
Min. to Max. Range
specified for the
selected Input Type
Holdback Type
(Default : Min or Max Range)
Alarm-1 Deviation Band
-999 to 999
or -999.9 to 999.9
(Default : 5.0)
Alarm-1 Window Band
3 to 999 or 0.3 to 999.9
(Default : 5.0)
Holdback Value
Alarm-1 Hysteresis
1 to 999 or 0.1 to 999.9
(Default : 2)
Alarm-1 Inhibit
No
PROFILE STATUS INFORMATION : PAGE 1
Yes
Lower Readout
(Default : Yes)
Prompt
Alarm-2 Type
None
Process
Low
Process
High
Deviation
Band
Window
Band
(Default : None)
Alarm-2 Setpoint
Min. to Max. Range
specified for the
selected Input Type
(Default : Min or Max Range)
Alarm-2 Deviation Band
-999 to 999 or
-999.9 to 999.9
(Default : 5.0)
Alarm-2 Window Band
3 to 999 or
0.3 to 999.9
(Default : 5.0)
Alarm-2 Hysteresis
1 to 999 or
0.1 to 999.9
(Default : 2.0)
Alarm-2 Inhibit
No
Yes
(Default : Yes)
ON-LINE ALTERATION PARAMETERS : PAGE 2
Settings
Effect on the running segment
Parameters
(Default Value)
Time Interval
RAMP:- Altering the time
Disable
interval shall immediately
affect the 'Ramp Rate' for the
Enable
current segment.
(Default : Disable)
SOAK:- Elapsed time so far is
ignored and the soak timer
1 to 16
starts counting down to 0 from
(Default : 16)
the altered time interval value.
1 to 9999
Holdback Type
The modified Holdback Band
(Default : 1)
Type is applied immediately on
the current segment.
No
Holdback Value
The modified Holdback Band
Value is applied immediately
Yes
on the current segment.
(Default : Yes)
No
USER LINEARISATION PARAMETERS : PAGE 33
Yes
Effect on the running segment
Parameters
(Default : No)
Code
0 to 9999
Abort
(Default : 0)
Continue
User Linearisation
Disable
(Default : Continue)
Enable
(Default : Disable)
Total Break
Settings
1 to 32
Points
(Default Value)
(Default : 2)
1 to 16
(Default : 1)
Break Point
Number
1 to 32
Min. to Max. Range
(Default : 1)
specified for the
selected Input Type
Actual Value for
(Default : -199)
Break Point
-1999 to 9999
(X co-ord)
(Default : Undefined)
0 to 9999 Minutes
(Default : 0)
Derived Value for
Break Point
None
-1999 to 9999
(Y co-ord)
(Default : Undefined)
Up
Down
Both
(Default : None)
1 to 999
(Default : 1)
Upper Readout
Information
Active Segment Number
Segment Type
Target Setpoint
Ramping Setpoint
Balance Time
Balance Repeats
TABLE- 1
Option
Range (Min. to Max.)
Resolution
0 to +960°C / +32 to +1760°F
J Type T/C
-200 to +1376°C / -328 to +2508°F
K Type T/C
-200 to +385°C / -328 to +725°F
T Type T/C
0 to +1770°C / +32 to +3218°F
R Type T/C
Fixed
0 to +1765°C / +32 to +3209°F
1°C / 1°F
S Type T/C
0 to +1825°C / +32 to +3218°F
B Type T/C
0 to +1300°C / +32 to +2372°F
N Type T/C
Reserved for customer specific
Thermocouple type not listed
above.
User settable
-199 to +600°C / -328 to +1112°F
1°C / 1°F
or
or
-199.9 to 600.0°C / -199.9 to 999.9°F
RTD Pt100
0.1°C / 0.1°F
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC
0 to 200mV DC
User settable
-1999 to +9999 units
1 / 0.1 / 0.01/
0.001 units
0 to 1.25V DC
0 to 5.0V DC
0 to 10.0V DC
1 to 5.0V DC
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar - 401 210.
T: 0250 - 2391722/33/37/42
M: 07498799226
09321985369
E:
sales@ppiindia.net,
support@ppiindia.net

Advertisement

loading
Need help?

Need help?

Do you have a question about the neuro 102 EX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PPI neuro 102 EX

  • Page 1 Operation Manual neuro 102 EX This brief manual is primarily meant for quick reference to wiring Enhanced Universal Single Loop connections and parameter searching. For more details on Process Controller operation and application; please log on to www.ppiindia.net CONFIGURATION PARAMETERS : PAGE 12...
  • Page 2 FRONT PANEL LAYOUT ENCLOSURE ASSEMBLY JUMPER SETTINGS Front Panel INPUT TYPE & OUTPUT-1 neuro 102 EX Upper Readout Lower Readout Jumper Setting - A (Input Type) Alarm-2 Status Profile Status AL2 SBY PRF Latching Slot Ramp / Soak Status Alarm-1 Status...