4.10.4. Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well as
software and hardware information
Item
BOILER 1
BOILER 2
BOILER 3
BOILER 4
IGNITION
VENT WALL
LIMIT TEMP
EMS Vdc
FIRE RATE
SPEED
OUTLET MAX
OPERATOR
DIFF
Pump Post
FLAME CUR
MASS
IDENTITY
IGN TYPE
ID CARD
ERROR CODE
ERROR HISTORY
Application
ALL
Enables Boiler for operation
CASCADE
Enables Boiler for cascade operation
CASCADE
Enables Boiler for cascade operation
CASCADE
Enables Boiler for cascade operation
IDLE=no CFH;
PREP=pre-purge or inter-purge between trials for ignition;
IGN=trial for ignition;
BURN=burner operating;
POST=post purge;
HARD=a hard lockout fault has occurred requiring manual reset (Ignition
ALL
Lockout or manual high limit); and
SOFT=a soft lockout fault has occurred which interrupts the heating cycle
(any safety other than ignition or manual high limit).
The CFH will resume after the soft lockout fault has been corrected and a
15 min. waiting period has expired.
Monitors vent temperature and adjust firing rate if vent temperature
ALL
approaches limit for vent material installed/selected.
ALL
Current Outlet-Limit temperature
ALL
Current EMS signal in Volts DC
ALL
PIM firing rate
ALL
Blower speed in revolutions per minute (rpm)
Defines Max Outlet temperature offset above Target Setpoint (Press and
H Mode 1, 2, 3
hold up and down arrows for 3 seconds to enable adjustment). See VERSA
IC control manual (5000.72).
ALL
Operator Potentiometer setting on PIM
ALL
Current auto differential – Fixed by PIM
ALL
Sets the length of the boiler pump purge
ALL
Flame current in micro-amps (µA)
ALL
Thermal mass recovery see VERSA IC control manual (5000.72).
ALL
Identifies the unit as boiler, water heater or pool heater
ALL
PIM Board type
ALL
Identifies Raypak Identity Card
ALL
Current Error Code
ALL
Up to 15 Error Codes can be logged