INSTALLATION & OPERATING
ULTRA HIGH EFFICIENCY
Models 1005A–2005A
Types H, WH & P
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, exposure to hazardous materials* or loss of
life. Review the information in this manual carefully. *This unit contains materials that
have been identified as carcinogenic, or possibly carcinogenic, to humans.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future
reference.
CATALOG NO. 3400.552
INSTRUCTIONS
Effective: 08-02-13
Replaces: NEW
P/N 241513 Rev. 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Xtherm 1505A and is the answer not in the manual?

Questions and answers

Summary of Contents for Raypak Xtherm 1505A

  • Page 1 INSTALLATION & OPERATING INSTRUCTIONS ULTRA HIGH EFFICIENCY Models 1005A–2005A Types H, WH & P WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials* or loss of life. Review the information in this manual carefully. *This unit contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans.
  • Page 3: Table Of Contents

    CONTENTS Venting Installation Tips WARNINGS Venting Configurations BEFORE INSTALLATION Product Receipt Outdoor Installation Model Identification Controls Ratings and Certifications User Interface Installations at Elevation WIRING DIAGRAM Component Locations START-UP General Information Pre Start-up Start-Up GENERAL SAFETY Time/Temperature Relationships in OPERATION Scalds Lighting Instructions To Turn Off Gas To Appliance...
  • Page 4: Warnings

    WARNINGS Pay Attention to These Terms Indicates the presence of immediate hazards which will cause severe DANGER: personal injury, death or substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause WARNING: severe personal injury, death or substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause CAUTION: minor personal injury or product or property damage if ignored.
  • Page 5: Before Installation

    If, after reviewing this manual, you still have questions Ratings and Certifications which this manual does not answer, please contact your local Raypak representative or visit our website at www.raypak.com. Standards: Thank you for purchasing a Raypak product. We hope •...
  • Page 6: Component Locations

    Component Locations HEATER PUMP INJECTOR PUMP(S) Fig. 3: Component Locations – Rear Panels omitted for clarity Fig. 1: Component Locations – Side Top panel, blower and gas train omitted for clarity Fig. 4: Component Locations – Top General Information Water Conn Gas Conn Vent...
  • Page 7: General Safety

    GENERAL SAFETY To meet commercial hot water use needs, the high limit safety control on this water heater will shut off the main gas valve before the outlet temperature reaches 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec- ommended initial setting for the temperature control is 125°F.
  • Page 8: Installation

    INSTALLATION CAUTION: This heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliances or to the Installation Codes structure. When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained, be installed under the Installations must follow these codes: appliance.
  • Page 9: Combustion And Ventilation Air

    The combustion air intake elbow MUST be used for outdoor installations. It is shipped loose to be installed on the air filter intake at the rear of the heater at the job site. The elbow MUST be oriented with the opening facing downward (shipped loose).
  • Page 10 Fig. 7: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations U.S. Installations Canadian Installations Clearance above grade, veranda, porch, 1 ft (30 cm) 1 ft (30 cm) deck, or balcony 4 ft (1.2m) below or to side Clearance to window or door that may be of opening;...
  • Page 11: Conventional Combustion Air Supply

    3. In cold climates, and to mitigate potential freeze- Fig. 12: Install the Intake Air Collar up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula- 6. Replace all the access panels.
  • Page 12 9. In cold climates, and to mitigate potential freeze- The minimum dimension of air openings shall not be up, Raypak highly recommends the installation of less than 3 in. (76 mm) in any direction. Where ducts a motorized sealed damper to prevent the circula-...
  • Page 13: Water Piping

    160 psi operating pressure. WARNING: Care must be taken to ensure that the However, Raypak does recommend hydrostatic test- equipment room is not under negative pressure ing of the piping connections to the heater and the rest conditions.
  • Page 14: Hydronic Heating

    It is highly recommend- ed that the piping be insulated. Feedwater Regulator Raypak recommends that a feedwater regulator be in- stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual shut-off valve as required by local codes.
  • Page 15 System Model 1005 Model 1505 Model 2005 Return Temp Supply Temp Minimum Pipe Size Supply Temp Minimum Pipe Size Supply Temp Minimum Pipe Size (°F) (°F) <80' equiv. 80-200' equiv. (°F) <80' equiv. 80-200' equiv. (°F) <80' equiv. 80-200' equiv. 2"NPT 2 1/2"NPT 2"NPT...
  • Page 16: Applications & Modes

    System Pump (P2) runs whenever the system is be used. Raypak heaters are high-recovery, low-mass enabled for heating and the outdoor air temperature is heaters which are not subject to thermal shock.
  • Page 17: Domestic Hot Water

    NOTE: MODE 1 can also be used for process heat- ing applications in conjunction with a buffer/storage tank when operating temperatures above 160°F are required. Care must be given to ensure water hard- ness is no more than 15 grains per gallon for scale free operation.
  • Page 18 Tank Model 1005 / t f Minimum Tubing Size Med Sup. Hard Sup Minimum Tubing Size / t f Minimum Tubing Size (°F) Temp (°F) Temp (°F) <80' equiv. 80-200' equiv. Temp (°F) Temp (°F) Temp (°F) <80' equiv. 80-200' equiv. Sup. Temp (°F) <80' equiv.
  • Page 19: Pool Heating

    Automatic Chemical Feeders All chemicals must be introduced and completely dilut- ed into the water before being circulated through the heater. High chemical concentrations will result when the pump is not running (e.g. overnight). NOTE: High chemical concentrates from feeders CPVC, COPPER OR BRASS that are out of adjustment will cause rapid corrosion AUTO LIMIT...
  • Page 20 Other Pool and Spa Recommended Level(s) Fiberglass Pools Fiberglass Spas Types Water Temperature 68-88°F (20-31°C) 89-104°F (31-40°C) 68-104°F (20-40°C) 7.3-7.4 7.3-7.4 7.6-7.8 Total Alkalinity (ppm) 120-150 120-150 80-120 Calcium Hardness (ppm) 200-300 150-200 200-400 Salt (ppm) 3000 Maximum 3000 Maximum 3000 Maximum Free Chlorine (ppm)* Total Dissolved Solids...
  • Page 21: Gas Supply

    Gas Supply CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural DANGER: Make sure the gas on which the heater and propane gases is recommended. Apply will operate is the same type as specified on the sparingly only on male pipe ends, leaving the two heater’s rating plate.
  • Page 22: Electrical Power Connections

    1-1/4” NPT 1-1/2” NPT 2” NPT 2-1/2” NPT Model No. 1005A 1505A 2005A • Natural Gas – 1,000 BTU/ft , 0.60 specific gravity at 0.5 in. WC pressure drop • Propane Gas – 2,500 BTU/ft , 1.53 specific gravity at 0.6 in. WC pressure drop Table I: Maximum Equivalent Pipe Length XTherm heaters are wired for 120VAC single phase Manifold Gas Pressure...
  • Page 23: Making The Electrical Connections

    WARNING: Using a multi-meter, check the following voltages at the circuit breaker panel prior to connecting any equipment. Make sure proper polarity is followed and house ground is proven. (See Fig. 19.) Check the power source: AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX BC = <1 VAC Maximum Fig.
  • Page 24: Field Wiring Connection

    Fig. 23: Wiring Location Fig. 24: Locator Dimples for Optional Components NOTE: A grounding electrode conductor shall be contact closure (including a remote thermostat) across used connect equipment grounding these terminals will enable the XTherm unit to run. conductors, the equipment enclosures, and the Caution should be used to ensure neither of the termi- grounded service conductor to the grounding nals becomes connected to ground.
  • Page 25 3. Connect the indirect tank sensor to the terminals than 4 connected boilers, an external sequencer marked INDIRECT DHW SENSOR (see wiring such as the Raypak Temp Tracker Mod+ Hybrid diagram). Caution should be used to ensure nei- can be used.
  • Page 26 MASTER FOLLOWERS VERSA MASTER Fig. 27: XTherm Cascade System Wiring Cascade System Pump and Sensor Wiring 1. On the boiler designated as the Master, connect the system pump enable wiring to the terminal block at the rear of the unit. The connections are dry contacts rated for pilot duty only (5A maxi- mum).
  • Page 27: Venting

    XTherm products. A field installed vent the maximum voltage across the contacts is 30 VAC or adapter supplied by Raypak (option D-33) must be 30 VDC. See the Field Wiring as shown in Fig. 25. used to ensure a proper seal of the flue and conden- sate.
  • Page 28 CAUTION: Condensate drains for the vent piping NOTE: During winter months check the vent cap are required for installations of the XTherm. Follow and make sure no blockage occurs from build-up of vent manufacturer instructions for installation and snow or ice. location of condensate drains in the vent.
  • Page 29 Combustion Exhaust Heater Venting Certified Combustion Air Air Supply Configuration Category Materials Inlet Material Vertical Venting From Inside Building CAT IV (Non-Direct Venting) Horizontal Through- (AL29-4C) the-Wall Venting CPVC Vertical Galvanized Steel Polypropylene* Venting From Outside Building (Direct Venting) Horizontal Through- CPVC the-Wall Venting * Only Centrotherm polypropylene material is approved for use with the XTherm.
  • Page 30: Venting Installation Tips

    Total Effective Air Inlet Certified Combustion Air Model Vent Size Length (ft) Max. Length* (ft) Vent Intake Pipe (in.) Material Material Min. Max. 6” Ø 8” Ø 10” Ø Category IV Galvanized 1005A 100** (AL29-4C) Steel, PVC, 1505A CPVC ABS, 85** Polypropylene*** CPVC...
  • Page 31 Common Venting 8’ OR LESS The NFGC does not address sizing guidelines for the common venting of multiple Category IV heaters. This is covered in the NFGC under “Engineered Vent Sys- tems”. Table N provides the volume of flue products at full fire for the calculation of appropriate vent sizing and extractor for common venting.
  • Page 32 Horizontal Through-the-Wall and Direct Venting (Category IV) Fig. 27: Horizontal Through-the-Wall Direct Venting Fig. 25: Horizontal Through-the-Wall Venting CAUTION: This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system may cause a non-wrrantable failure.
  • Page 33 1 ft above ground level and above normal snow levels. The Raypak-approved The vent must be installed to prevent the potential ac- stainless steel flue direct vent cap MUST be used cumulation of condensate in the vent pipes.
  • Page 34: Outdoor Installation

    cap to the side of the adjacent vent cap(s). 84. Install above grade level and above normal snow levels. Combustion air supplied from outdoors must be free of particulate and chemical contaminants. To avoid a Vent terminal must be at least 3 ft above any blocked flue condition, keep the vent cap clear of forced air inlet located within 10 ft.
  • Page 35 Top View SIDEWALL VENT TERMINATION OPTION D-15 STAINLESS STEEL CONDENSING HEAT EXCHANGER Fig. 30: PVC Vent Adapter 38°F, the VERSA starts the burner at the minimum fir- DANGER: Primer, cleaner, and cements are ing rate. The burner cycle will terminate when both the extremely flammable.
  • Page 36 11) A special sidewall vent adapter/termination must cuts must be made at right angles to the pipe. Pipe be used as supplied by Raypak per our listing. must then be beveled for insertion into the adjoining socket to ease installation. All field cuts must be 12) Rooftop installations must use a category IV listed deburred.
  • Page 37: Controls

    3 times during a call for Raypak’s instructions. There is no cure time or wait heat. To reset the lock-out, press and release the time required.
  • Page 38: Flow Switch

    1 - OFF 2 - ON 3 - ON 4 - OFF 5 - OFF 120ºF 75ºF SETPOINT (B) INJECTOR PUMP WIRING S3 S2 S1 Com Fig. 38: High Limit (Manual Reset) High Limit—Auto Reset (Optional) This heater may be equipped with an optional adjust- able auto reset high limit temperature device.
  • Page 39 sure switch), as necessary. If the gas pressure regula- tor in the valve fails, the high gas pressure switch automatically shuts down the burner. Operation of either the High or Low Gas Pressure Switch will turn on an LED inside the switch housing. Push the top of the plastic switch housing as shown in Fig.
  • Page 40: User Interface

    User Interface Adjusting the XTherm Setpoint The user interface consists of several Menu options. Press the MENU button to scroll through the different To adjust the setpoint on the XTherm: menus in the interface. Press the ITEM button to scroll through available items within a selected menu.
  • Page 41 Item Application Range Description Default Enable or Disable the operation of boilers. 4 boiler range, 1 is BOILER 1 ON <> OFF enabled by default TARGET H MODE 1,2,3 RSET <> SETP RSET = Outdoor Reset, SETP =Setpoint SETP TANK SETP OFF, 50°F to 150°F Tank set point temperature 125°F...
  • Page 42 Boiler Menu The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well as software and hardware information Item Application Description IGNITION Current State of Ignition LIMIT TEMP Current Limit Temperature AUX TEMP H MODE 3 Current Auxiliary Temperature EMS Vdc Current EMS signal in Volts DC...
  • Page 43 Monitor Menu The Monitor Menu records and displays critical Boiler information, such as, Cycle times, Run times, and Maximum/Minimum temperature readings depending on the setup. Item Application Description RUN TIME Burner 1 Burner run time (hours). Press UP/DOWN for 1 sec to clear. Cycles Burner Number of burner cycles.
  • Page 44 MAX HEAT be set to OFF again by the user. (See VERSA IC Manual for details.) P/N 104901 Software number of the Raypak VERSA Resets to factory settings. Press UP and DOWN for 1 second to show CLR and load DEFAULTS factory defaults to all settings.
  • Page 45: Reset Ratio

    RESET RATIO The control uses the four following settings to determine the reset ratio: Boiler Start (Boil START) The Boil START temperature is the theoretical boiler supply water temperature that the heating system requires when the outdoor air temperature equals the OUT START temperature setting. The Boil START is typically set to the desired building temperature. Outdoor Start (OUT START) The OUT START temperature is the outdoor air temperature at which the control provides the Boil START water temperature to the system.
  • Page 46: Wiring Diagram

    WIRING DIAGRAM - Models 1005A–2005A...
  • Page 47: Start-Up

    START-UP BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell near the floor because some gas is heavier than air and will settle on the floor. NOTE: The following steps must be performed by a factory-trained technician.
  • Page 48: Start-Up

    Preparation 3. If the gas pressure is greater than 14.0 in. WC, turn off the main gas shut-off valve, upstream of the heater. WARNING: Do not turn on gas at this time. Start-Up Check Power Supply NOTE: The values in Tables T and V represent the With multi-meter at incoming power, check voltage conditions when the heater is at full firing rate at sea between:...
  • Page 49 Manifold Check User Test 1. Check manifold gas pressure at the gas valve out- Set DIP switch #1 on the VERSA IC control to “ON”. let pressure tap (connection “D” in Fig. 43). This Set USER TEST = ON in the 'ToolBox' Menu to start pressure should read per the values in Table U for the user test function.
  • Page 50 Leak Test Procedure: Dual-Seat Gas Safety Inspection Valve 1. Check all thermostats and high limit settings. Proper leak testing requires three pressure test points 2. During the following safety checks leave manome- in the gas train. Remove the upper front panel and ters hooked up, check and record.
  • Page 51 8. To test the fixed manual reset high limit built into the PIM™, first set dip switch #8 on the PIM™ to the ON position. This will activate a Commission Test Mode which will turn on the amber Alarm/Test LED on the PIM™. The fixed high limit setting is temporarily overridden to match the setpoint potentiometer position on the PIM™.
  • Page 52: Operation

    OPERATION d. Gas is on at the meter and the heater. e. Incoming dynamic gas pressure to the gas valve is NOT less than 4.0 in. WC for natural Lighting Instructions gas or propane gas. 1. Before operation, make sure you have read all of To Turn Off Gas To Appliance the safety information in this manual.
  • Page 53 2. Note the error code, either through the flash code WARNING: When servicing or replacing any on the PIM™ and/or from the Toolbox menu on the components of this unit be certain that: user interface, and reference the explanation of •...
  • Page 54 LED Error Code Listing Active errors detected are indicated by LED lights on the PIM™. LED Code Error Mode Recommended Troubleshooting Normal Operation Red LED steady ON, Check that the proper ID card is securely connected. Perform a ID Card Fault Green Power power and system restart.
  • Page 55: Maintenance

    MAINTENANCE Sensor Resistance Values Suggested Minimum Water Sensor / Outdoor Sensor Maintenance Schedule Water Temperature (°F) Resistance (ohms) 32550 Regular service by a qualified service agency and 25340 maintenance must be performed to ensure maximum operating efficiency. 19870 15700 Daily and monthly maintenance as outlined below may be performed by onsite maintenance staff.
  • Page 56: Preventive Maintenance Schedule

    3. Check that area is free from combustible materi- Weekly als, gasoline, and other flammable vapors and liquids. For low-pressure heaters, test low-water cut-off device. (With heater in pre-purge, depress the low 4. Check air filter and replace as necessary. water cut-off test button.
  • Page 57: Filter Maintenance

    (See “Manifold Check” on page 47.) 7. Test safety/safety relief valves in accordance with ASME Heater and Pressure Vessel Code Section IV. Filter Maintenance NOTE: Use Raypak replacement filters, kit number 012599F. • Inspect quarterly. • Replace as needed.
  • Page 58: Appendix

    APPENDIX • metal fabrication plants • beauty shops • refrigeration repair shops Inside Air Contamination • photo processing plants • auto body shops • plastic manufacturing plants All heaters experience some condensation during • furniture refinishing areas and establishments start-up. The condensate from flue gas is acidic. •...
  • Page 59: Important Instructions For The Commonwealth Of

    Important Instructions for the Commonwealth of Massachusetts The Commonwealth of Massachusetts requires compliance (b) EXEMPTIONS: The following equipment is exempt from with regulation 248 CMR 4.00 and 5.00 for installation of 248 CMR 5.08(2)(a)1 through 4: through – the – wall vented gas appliances as follows: 1.
  • Page 61: Start-Up Checklist

    RAYPAK PRODUCTS This start-up checklist is to be completely filled out by the service technician starting up the Raypak Boiler or Heater for the first time. All information may be used for warranty purposes and to ensure that the installation is correct.
  • Page 62: Warranty

    EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.