START
-
UP
1
.
Check
all
electrical connections
for
tightness.
2.
Check belt tension on
5
ton
units.
3.
Check
motor
screws for.
tightness.
4.
Check supply vollage on
all three phases.
A
variance of
more
than 10% from nameplate
rating
may
cause component failure and
will
void system warranty
.
5.
Check to see that the air filter is installed.
6.
Turn
unit
evaporator
on
and
an
check
for
the condenser
7.
Make
sure
the
unit is
level
.
proper
blower
section.
rotation
8.
Set thermostat so
it is
calling for
blower
on only.
both
for
9
.
Turn unit
on
.
The evaporator
blower
should
be
running.
Check
and
record
th
e
se amperages.
Make
sure they do not
e
xceed
the
nameplate
ratings.
10
.
11.
Turn
the
thermostat
at
l
ow.
The compressor will
come
on.
Check and record the compressor
amperage.
not
exceed the
nameplate
readings.
Make
sure
it
doe
s
l2.
Check and
record the suction
and
discharge
refr
i
gerant
pressures.
13 .
Turn
the thermostat to
high
to
check
and
record the amperage.
rating.
energize
the
heat
c
y
cle.
Compare to
the nameplate
l4.
Check
and record
the suction
and discharge
refrig
e
rant
pressures.
15.
Before completing
the start-up procedure,
check
to
make sure
the air
leaks
are
plugged.
16
.
Set
room thermostat
to
the desired
setting.
29
the