OPERATION MAINTENANCE AND PARTS MANUAL CELLU – KOOL SERIES MODEL TYPE SIZE CELHP HEAT PUMP 1 ½ TO 5 TON CELAC AIR CONDITIONER 1 ½ TO 5 TON COMPU – AIRE INC. 8167 BYRON RD. WHITTIER, CA 90606 PH : (562) 945 – 8971...
Page 2
--GETTING OTHER INFORMATION A N D PUBLICATIONS These publications can help you i n s t a l l the a i r conditioner o r heat pump. You can usually f i n d these a t your l o c a l 1 i b r a r y o r purchase them d i r e c t l y from the Be sure t o consult current e d i t i o n o f each standard.
Page 3
CELLU- K O O L AIR CONDITIONER ,LID H PUMP ELECTRIC HEATER (OPTIONAL) AIR OUT EVAPORATOR COIL EVAPORATOR BLOWER HIGH EFFICIENCY MOTOR COMPRESSOR HIGH 'AGE CONTROL PANEL CONDENSER COIL MODEL DESIGNATIOX HASE SINGLE PHASE YSTEM CAPACITY 2= 2TON, 4=4 TON YSTEM TYPE AC= AIR CONDITIONER HP= HEAT PUMP ERTICAL WALL HUNG UNITS...
COOLING COIL DAMPER BLADE EXHAUST AIR OUTSIDE A I R COND. A I R CONDENSER...
Page 7
GENERAL The equipment covered in this manual is to be installed by tralned, experienced service and installation technicians. The refrigerant system is conpletely assembled and charged. All internal wiring is complete. The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
FILTERS A 1-inch throwaway filter is supplied with each unit. The filter slides into position naklng it easy to service. This filter can be serviced from the outside by renoving the service d m . 1-inch washable filter and 2-'inch pleated filter are a h 0 available as optional accessories. The internal filter brackets are adjustable to accommodate the 2-inch filter the brackets apart to the required width and retightening the 4 screws.
Locate and nark lag bolt locations and bottom mounting bracket location, if desired. See Figure Book top rain flashing under back bend of top. Top rain flashing is shipped attached to the back of the unit on the right side. Position unit in opening and secure with 5/16 lag bolts: use...
Page 10
BE PLACED BEHIND TEE SIDE W O W I N G FLANGES UNDER FLASHING A BW1...
Page 11
ELECTRIC BEAT Side section view of supply air duct for wall naunted unit showing clearance to conbustible surfaces. WARNING clearance must This is required for the first 3 feet of ducting. It is important to insure that the Failure to do this could result in overheating the mnbuntible material and nay result in a fire.
Refer to the unit rating plate for wire sizing information and maximum fuse or "HACR Type" circuit breaker size. Each outdoor unit is marked with a "Minimum Circuit Ampacityw. This means sized to carry that amount of current. Depending on the that the field wiring used must two field power circuits required.
SEQUENCE OF OPERATION energized by manual fan sw~tch on subbase for constant a x circulation. solenoid coil on reversing valve controls heating cycle operation. one allowing "Auto" changeover fron cycle to cycle and the other constantly energizmg solenold coll during heating season and thus elininating pressure equalization nolse except during defrost, are to be used.
TROUBLESHOOTING SOLID STATE HEAT W COKFROC Turn on AC power supply to indoor and outdoor units. Turn thermostat blower switch to fan on--the indoor blower should start. (If it doesn't, troubleshoot indoor unit and correct problem). Turn thermostat blower switch to auto position. Indoor blower should stop. Set system switch to heat or cool.
Page 16
FAN BLADE SETTING DIMENSIONS Shown in the drawing below are the correct fan blade setting dimensions for proper a i r delivery across the service requiring renxral or adjustment in the fan andlor notor area require that the will dinensions below checked and blade adjusted in or out on the motor shaft accordingly.