Pentair VARISTAR SHX 30 Instruction Manual page 72

Cooling unit
Table of Contents

Advertisement

Pos: 5 0.3 /Te chni sche Daten/Ter motek/SH X/30 - Allgemein @ 243 \mod_1 42296 1963 530_1 8.docx @ 22 36166 @ @ 1
General data
Ambient conditions
Sound pressure level
Weight
Technical specification
Nominal cooling power
Chilling medium
Water circulation rate
Pressure loss inside the unit
Water inlet temperature
Volumetric air flow
Control temperature
Max. control deviation
Electrical data (AC version)
Supply voltage
Max. current consumption
Max. power consumption
Power consumption during normal operation
Series fuse (building)
Technical Data
Temperature for transport and storage when
completely empty or flushed with 35% glycol
Relative humidity for transport and storage (non-
Temperature outside of the cabinet during the
Cooling unit (cooling module and cabinet) kg
adjustable (in steps of 0.1)
adjustable emergency cooling of 0-8 K to
VARISTAR Cooling unit SHX 30
°C
%
condensing)
°C
operation (min./max.)
at 80% fan speed dB (A)
at 100% fan speed dB (A)
Cooling module kg
max.
max.
3
measured at 3 m
/h
3
measured at 4.3 m
/h
min./max.
max.
the set value
at 230V
at 115V
fan speed 100%
fan speed 80%
at 230V
at 115V
-25 ... +70
5 - 95
5 - 70
79
84
110
370
kW
30
-
Water, water-
glycol-mixture
(33% max.)
m³/h
4,3
bar
1,3
bar
3,0
°C
6 / 18
m³/h
5000
°C
18 - 50
K
4 (factory-set)
V
100-240 /
1 / N / PE
Hz
50/60
A
6
A
12
W
1000
W
750
A
D 10
A
D 16
72

Advertisement