Cooling Module; Rinsing Process - Pentair VARISTAR SHX 30 Instruction Manual

Cooling unit
Table of Contents

Advertisement

Pos: 3 5.31 / Übers chrifte n/1. 1/Kühlmodul @ 153 \mod_1 3675 70395 273_1 8.docx @ 15 6173 6 @ 2 @ 1
7.5

Cooling module

Pos: 3 5.32 / Übers chrifte n/1. 1.1/Spülvorgang @ 9 3\mod_ 12881 8108 5084_ 18.docx @ 1 04090 3 @ 3 @ 1
7.5.1

Rinsing process

Pos: 3 5.33 /Hi nweise/ Warnung Pers onen/Warnung - Gesundheitsgefa hr, Schutzkleidung (Ha nd-, Augens chutz, Atemmaske) @ 243 \mod_1 42296 1077 211_1 8.docx @ 22 35965 @ @ 1
Pos: 3 5.34 / Wartung/Ter motek/ Kühl modul s pülen @ 243\ mod_14 2296 1612 871_1 8.docx @ 223 6065 @ @ 1
Maintenance
WARNING
Health hazard!
The use of chemicals can present a health hazard.
Observe the safety data sheets.
Wear protective clothing as stated in the safety data sheet when handling
chemicals (e.g. safety goggles, face shield, respiratory equipment, safety gloves,
safety shoes, etc.).
When the cooling module is tilted and place on its side, all of the water connections must
be sealed since, otherwise, the medium that flows out can damage the electronic control
system.
Note
The cooling module can be flushed with a commercially available, glycol-based
anti-freeze agent (e.g. GLYSANTIN by BASF).
Ensure that the anti-freeze agent is compatible with the pipe system of the
building.
Observe the safety data sheet.
1.
Remove the cooling module.
2.
Seal the condensate outlet.
3.
Connect a pressure pump (hand pump) to the feed flow.
4.
Connect a hose (approx. 3 m) to the return flow.
5.
Open the actuator of the control valve by hand (see the procedure that is described
in the "Start-up/Venting" section).
6.
Insert the suction hose of the pressure pump and the return flow hose of the
cooling module into a vessel with a capacity of approximately 15 litres.
7.
Fill the vessel with approximately 3.5 litres of glycol (this ensures protection against
freezing up to approximately -20°C).
8.
Switch the pump on and flush the cooling module for 5 to 15 minutes with glycol.
9.
Switch the pump off and open the vent valve of the heat exchanger.
Note
If the pump has a non-return valve, the pump must be replaced with a hose.
VARISTAR Cooling unit SHX 30
62