Mask contents:
OVERVIEW
Temperature
Valve opening
Sensor selection
Fan power
Chiller
Pos: 3 4 /-- leer --/=== ===== @ 1\mod2 6_18. docx @ 2718 8 @ @ 1
Operation
Note
Default values are indicated in brackets ( ).
18-40°C
(22°C)
64-104°F
(71.6°F)
%
=> top
=>
average
=>
bottom
<= top
<=
average
<=
bottom
External
(=>
average)
30-100%
(80%)
OFF/ON
Description
This screen is also the start screen when the system is switched
on. Display and modification of system-specific data.
Indication of the actual temperature.
Adjustment of the default temperature.
The limits of the setting range of the default values (MIN, MAX)
can be adjusted in the mask "Configuration".
Indication of the opening degree of the cooling valve in per
cent.
Selection of the temperature sensor for the determination of
the actual temperature and for the temperature control.
<= bottom:
Temperature sensor in the air outlet, position
in the lower cabinet area
<= average:
Determination of the actual temperature by
averaging the temperatures of the
upper/lower cabinet area
<= top:
Temperature sensor in the air outlet, position
in the upper cabinet area
=> bottom:
Temperature sensor in the air inlet, position in
the lower cabinet area
=> average:
Determination of the actual temperature by
averaging the temperatures of the
upper/lower cabinet area
=> top:
Temperature sensor in the air inlet, position in
the upper cabinet area
External:
External temperature sensor (option)
Adjustment of the set fan speed.
30%:
minimum set fan speed
100%: maximum set fan speed
Activation/deactivation of the cooling module
ON:
Cooling module switched on
OFF:
Cooling module switched off
VARISTAR Cooling unit SHX 30