Troubleshooting; Unit Will Not Start Or Starts Then Stops; Unit Operates Long Or Continuously In Cooling - Carrier PrimeLINE 69NT40-561-200 Operation And Service Manual

Container refrigeration units
Hide thumbs Also See for PrimeLINE 69NT40-561-200:
Table of Contents

Advertisement

CONDITION
6.1

UNIT WILL NOT START OR STARTS THEN STOPS

No power to unit
Loss of control power
Component(s) not operating
Compressor hums, but does
not start
6.2

UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING

Container
Refrigeration system
SECTION 6

TROUBLESHOOTING

POSSIBLE CAUSE
External power source OFF
Start-Stop switch (ST) OFF or defective
Circuit breaker tripped or OFF
Autotransformer not connected
Circuit breaker OFF or defective
Control transformer defective
Fuse (F3A/F3B) blown
Start-Stop switch (ST) OFF or defective
Evaporator fan motor internal protector open
Condenser fan motor internal protector open
Compressor internal protector open
High pressure switch open
Heat termination thermostat open
Malfunction of current sensor
Low line voltage
Single phasing
Shorted or grounded motor windings
Compressor seized
Hot load
Defective box insulation or air leak
Shortage of refrigerant
Evaporator coil covered with ice
Evaporator coil plugged with debris
Evaporator fan(s) rotating backwards
Air bypass around evaporator coil
Controller set too low
Compressor service valves or liquid line shutoff valve
partially closed
Dirty condenser
Compressor worn
Current limit (function code Cd32) set to wrong value
Economizer solenoid valve malfunction
Digital unloader valve stuck open
Electronic expansion valve
6–1
REMEDY/REFERENCE
SECTION
Turn on
Check
Check
Section 5.2.2
Check
Replace
Check
Check
Section 7.17
Section 7.9
Section 7.9
Section 6.7
Replace
Replace
Check
Check
Section 7.9
Section 7.9
Normal
Repair
Section 7.3
Section 6.6
Section 7.15
Section 7.15/Section 7.17
Check
Reset
Open valves completely
Section 7.11.2
Section 7.9
Section 4.3.25
Section 7.25
Replace
Replace
T-362