6. "CLEAr" is displayed if all alarms are inactive. The alarm queue may then be cleared by pressing ENTER.
The alarm list will clear and "-----" will be displayed.
AL26 is active when none of the sensors are responding. Check the connector at the back of the
controller, if it is loose or unplugged, reconnect it, then run a pre-trip test (P5) to clear AL26.
4.6

PRE-TRIP DIAGNOSTICS

Pre-Trip Diagnostics is an independent controller function that suspends normal refrigeration controller activities
and provides preprogrammed test routines. The test routine can be run in Auto Mode, which automatically per-
forms a pre programmed sequence of tests, or Manual Mode, which allows the operator to select and run any of
the individual tests.
Pre-trip inspection should not be performed with critical temperature cargoes in the container.
When the pre-trip key is pressed economy, dehumidification and Bulb Mode will be deactivated. At
the completion of the pre-trip test, economy, dehumidification and Bulb Mode must be reactivated.
A pre-trip test may be initiated by use of the keypad or via communication, but when initiated by communication the
controller will execute the entire battery of tests (auto mode).
At the end of a pre-trip test, the message "P," "rSLts" (pretest results) will be displayed. Pressing ENTER will allow
the user to see the results for each of the sub-tests. The results will be displayed as "PASS" or "FAIL" for each test
run to completion.
A detailed description of the pre-trip tests and test codes is provided in
are provided in
Section
5.10.
4.7

DATACORDER

4.7.1

Description

Carrier Transicold "DataCORDER" software is integrated into the controller and serves to eliminate the tempera-
ture recorder and paper chart. DataCORDER functions may be accessed by keypad selections and viewed on the
display module. The unit is also fitted with interrogation connections (see
Carrier Transicold DataReader to download data. A personal computer with Carrier Transicold DataLINE software
installed may also be used to download data and configure settings.
The DataCORDER consists of:
Configuration Software
Operational Software
Data Storage Memory
Real Time Clock (with internal battery backup)
Six Thermistor Inputs
Interrogation Connections
Power Supply (battery pack)
The DataCORDER performs the following functions:
a. Logs data at 15, 30, 60 or 120 minute intervals and stores two years of data (based on one hour interval).
b. Records and displays alarms on the display module.
c. Records results of pre-trip testing.
CAUTION
!
CAUTION
!
Table
4–15
4–7. Detailed operating instructions
Figure
4.1) which may be used with the
T-362