14. Reinstall sensor. Refer to:
Section 7.28.3
- For STS and SRS Reinstallation
Section 7.28.4
- For RRS and RTS Reinstallation
Section 7.28.5
- For DTS Reinstallation
Section 7.28.6
- For ETS1 and ETS2 Reinstallation
The P5 Pre-Trip test must be run to deactivate probe alarms (refer to
7.28.3
Sensor STS and SRS Reinstallation
To properly position a unit supply sensor (Supply Temperature Sensor STS or Supply Recorder Sensor SRS), the
sensor must be fully inserted into the probe holder. This positioning will give the sensor the optimum amount of expo-
sure to the supply air stream, and will allow the Controller to operate correctly. Insufficient probe insertion into the
probe holder will result in poor temperature control due to the lack of air flow over the sensor.
It is also necessary to ensure that the probe tip does not contact the back panel. The design minimum clearance of
6 mm (1/4 inch) should be maintained (see
7.28.4
Sensor RRS and RTS Reinstallation
Reinstall the return sensor (Return Temperature Sensor RTS or Return Recorder Sensor RRS), as shown in
ure
7.23. For proper placement of the return sensor, be sure to position the enlarged positioning section of the sen-
sor against the side of the mounting clamp.
NOTE
Figure
7.22).
Figure 7.22 Supply Sensor Positioning
Sensor Wire
Cap & Grommet Assembly
Probe Holder
Supply Sensor
Figure 7.23 Return Sensor Positioning
Mounting
Clamp
7–39
E v a p o r a t o r B a c k
Panel
Supply Air
Stream
6mm (1/4")
Return
Sensor
1.50 in.
(38.1cm)
Section
5.10).
[
T-362
Fig-