Flue Outlet Direction
The flue connection on this water heater can be repositioned from the left hand side to the right hand
side if required.
Ensure the water heater is isolated from the mains power supply.
Remove the 18 screws holding the fan cover assembly to the water heater body and the 6 screws
around the flue connection.
Remove the fan cover assembly from the water heater.
Lift and rotate the fan exhaust assembly through 180
provided to accommodate full rotation of the fan exhaust assembly.
Ensure the electrical cable is clear of the combustion chamber opening and cannot be
pinched when replacing the fan cover assembly.
Replace the fan cover assembly in the new direction and replace all screws

GAS INLET

The pipe work must be cleared of foreign matter before connection and purged before attempting to
light the water heater. An isolation valve and disconnection union must be used to allow servicing and
removal of the water heater. Refer to AS 5601 for the correct pipe sizing.
Always isolate the water heater before pressure testing the gas supply system. Disconnect
the water heater after the isolating cock to prevent the risk of serious damage to the gas
train. Warranty does not cover damage of any nature resulting from failure to observe this
precaution. Refer to rating label for gas types and pressures.
The heater and its gas connection must be thoroughly leak tested before placing in operation. Use
soapy water and a manometer for leak test.
Do not use an open flame to check for gas leaks.
DANGER!
INSTALLLATION
12