TO TURN OFF THE WATER HEATER

1. Turn off the power supply to the water heater at the isolation switch.
EMERGENCY SHUT-DOWN
1. Turn off the power supply to the water heater at the isolation switch.
2. Turn off the gas isolation valve at the inlet to the water heater or the main gas supply.
CHECK FOR NORMAL OPERATION
With the water heater operating, remove the door and make a visual check of the burners. The
flame should be blue with a well-defined pattern.
A yellow or floating flame indicates restricted air openings, incorrect gas type, incorrect orifice size
or possible excessive draught.
Observe for any indication of soot. The presence of soot accumulation would indicate an abnormal
operating condition.
Should abnormalities be observed, turn off the water heater and contact Rheem Service or your
nearest Accredited Service Agent.
Operation of the water heater due to poor combustion will result in rapid and severe
damage, which is not covered by warranty.
LOCATION OF CONTROLS
(6)
located here for commissioning purposes.
OPERATION
(2)
1. FLAME FAILURE RESET: This is a combination
reset button and indicator lamp. It indicates, when
illuminated, that the ignition system has shutdown
on its safety control. During normal operation the
lamp is out and the button will not require any
operation.
2. TEMPERATURE CONTROL: This may vary with
the type of Heater installed and is explained later in
this section.
3. FLOW SWITCH: (Located in the return header)
This device will shut off power to the heater internal
controls in the event of low or no water flow.
4. GAS VALVE ISOLATION SWITCH: (Located under
the control panel behind the door) Used to isolate
the gas valve during the commissioning process
only.
5. FAN ISOLATION SWITCH: (Located under the
control panel behind the door) Used to isolate the
fan during the commissioning process only.
6. FAN PROVING PRESSURE SWITCH: Used to
prove fan operation prior to ignition. Test point
29