INSTALLLATION
ELECTRICAL SUPPLY
The electrical installation must comply with AS/NZS 3000 and any local requirements.
This water heater must be hard wired to a 240V AC 50 Hz M.E.N. (multiple earthed neutral) mains
power supply with an all pole isolating switch installed adjacent to and accessible from the water
heater (refer to AS 5601, 5.2.11). A suitable warning label must be affixed to the water heater if there
are additional control circuits not isolated by this switch. This label should direct the service person to
the isolation switch for that circuit.
Do not locate conduits across the doors, control panel or the top of the water heater.
Where conduit is to be mounted on the water heater cabinet there must be a 10mm air gap between
20