Specifications - Allen-Bradley 1794-IB16D Installation Instructions Manual

Flex i/o digital input and output modules with diagnostics
Hide thumbs Also See for 1794-IB16D:
Table of Contents

Advertisement

16 FLEX I/O Digital Input and Output Modules with Diagnostics
DeviceNet network, and the ControlNet network. Note: You can use the Module
Connection or Rack Connection when used in a ControlNet system.
Image Table Memory Map for the 1794-OB16D Module
Dec
15
14
Oct
17
16
Read 1
Not used
Write 2
O15
O14
Where
O = Output
Diagnostic
Bit 00 = Module error;
Status
Bit 01 = External power reverse polarity error;
Bit 02 = Output short error;
Bit 03 = Output open wire error

Specifications

Specifications – 16 Input Module w/ Diagnostics, 1794-IB16D
Meets IEC 3 24V DC input specifications
Attribute
Number of inputs
Recommended terminal base unit
On-state voltage, min
On-state voltage, nom
On-state voltage, max
On-state current, min
On-state current, max
Off-state voltage, max
Off-state current, max
Nominal input impedance
Isolation voltage
(1)
Input filter time
Off to On
On to Off
Publication 1794-IN096D-EN-P - June 2018
13
12
11
10
15
14
13
12
O13
O12
O11
O10
Value
16, current, sinking
1794-TB32, 1794-TB32S, 1794-TB62DS, 1794-TB62EXD4X15
10V DC
24V DC
31.2V DC
2.0 mA
1.5 mA
5.0V DC
1.5 mA
3.1 kΩ
50V (continuous), Basic Insulation Type
Type tested @ 2121V DC for 2 s, between field side and system
No isolation between individual channels
Refer to
9
8
7
6
11
10
7
6
O9
O8
O7
O6
Setting the Input Filter Time
5
4
3
2
5
4
3
2
Read Diagnostic Status
O5
O4
O3
O2
table.
1
0
1
0
O1
O0