FLEX I/O Digital Input and Output Modules with Diagnostics
Setting the Input Filter Time
To set the input filter time, set the associated bits in the output image (complementary
word) for the module.
15
O:010
Write filter time on system startup.
I:000
00
Input Filter Time
Bits
10
09
08
0
0
0
0
0
1
0
1
0
0
1
1
1
0
1
1
0
1
1
1
0
1
1
1
Configuring Your 1794-OB16D Output Module
Configure your output module by setting bits in the configuration word (word 3). This
module is compatibility with the Remote I/O network, with 1794-ASB series D or later,
14 13
12
11 10
9
8
7
1794-IB16D
FT = 0-15
1794-IB16D
Description
Filter Time for inputs 0...15
Filter Time 0 (Default)
Filter Time 1
Filter Time 2
Filter Time 3
Filter Time 4
Filter Time 5
Filter Time 6
Filter Time 7
6
5
4
3
2
1
0
FLL
Fill File
Source
#O:010
Destination
1
Length
12
11
10
9
8
7
6
0
1
1
Publication 1794-IN096D-EN-P - June 2018
Dec.
Write FT to complement
of input module.
5
= 5 Octal or 5 Decimal
Filter Time
Off to On /
On to Off
0.25 ms
0.5 ms
1 ms
2 ms
4 ms
8 ms
16 ms
32 ms
15