FLEX I/O Digital Input and Output Modules with Diagnostics
Environmental Specifications
Attribute
Operating temperature
Temperature, surrounding air,
max.
Storage temperature
Relative humidity
Vibration
Shock, operating
Shock, nonoperating
Emissions
ESD immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
Value
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F)
55 °C (131 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
IEC60068-2-27 (Test Ea, Unpackaged shock):
30 g
IEC60068-2-27 (Test Ea, Unpackaged shock):
50 g
CISPR 11:
Group 1, Class A (with appropriate enclosure)
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Publication 1794-IN096D-EN-P - June 2018