FLEX I/O Digital Input and Output Modules with Diagnostics

Diagnostics

See configuration information below for location of diagnostic bits.
Note: Each unused sensor port requires a dummy resistor to mask the channel diagnostic
function.
Diagnostic Functions for the 1794-IB16D
Ext.
Wiring
Power
OFF
Open
Short
Normal
ON
Open
Short
Normal
REV
Open
Short
Normal
The module monitors each sensor-power port for current and voltage. It turns on the channel red LED and
sets (1) the error bit when 1) the module detects a short circuit (no voltage at the sensor-port), and 2) the
module detects an open wire ( no current at the sensor-port).
Input
Channel
Status
LED
Status
Off
Off
On
Off
Off
Off
On
Off
Off
Off
On
Off
Off
RED
On
RED/YEL
Off
RED
On
RED/YEL
Off
Off
On
YEL
Off
Off
On
Off
Off
Off
On
Off
Off
Off
On
Off
Open
Short
Wire
Error Bit
Error Bit
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
0
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Publication 1794-IN096D-EN-P - June 2018
Rev.
Module
Error Bit
Error
Bit/LED
0
0/OFF
0
0/OFF
0
0/OFF
0
0/OFF
0
0/OFF
0
0/OFF
0
1/RED
0
1/RED
0
1/RED
0
1/RED
0
0/OFF
0
0/OFF
1
1/RED
1
1/RED
1
1/RED
1
1/RED
1
1/RED
1
1/RED
11