ATTENTION: Do not remove or replace a Terminal Base unit while power is
applied. Interruption of the backplane can result in unintentional operation or
machine motion.
Connecting Wiring for the 1794-OB16D Module
use with 1794-TB2, 1794-TB3, or 1794-TB3S Terminal Base
1.
Connect individual output wiring to numbered terminals on the 0-15 row (A) as
indicated in the Wiring Connections for 1794-OB16D table.
2.
Connect the associated common for each output to the corresponding terminal
on the 16-33 row (B) as indicated in the Wiring Connections for 1794-OB16D
table. The common terminals of row (B) are internally connected together.
3.
Connect +V DC power to terminal 34 on the 34-51 row (C). The power
terminals of row (C) are internally connected together.
4.
Connect DC common (COM) to terminal 16 on the 16-33 row (B).
5.
If daisychaining power to the next terminal base, connect a jumper from terminal
51 (+V DC) on this base unit to terminal 34 on the next base unit.
6.
If continuing DC common to the next base unit, connect a jumper from terminal
33 (common) on this base unit to terminal 16 on the next base unit.
1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-OB16D
0
1
16
17
18
-V
Common
34
35
Voltage
In +V
-V (Supply common) = Terminals B-16...B-33
+V (Supply +voltage in) = Terminals C-34...C-51
Use B-33 and C-51 for daisychaining to next terminal base unit
FLEX I/O Digital Input and Output Modules with Diagnostics
Outputs
2
3
4
5
6
7
19
20
21
22
23
24
Commons
36
37
38
39
40
41
Terminals 35...50 not available on 1794-TB2
Voltage
8
9
10
11
12
13
25
26
27
28
29
30
42
43
44
45
46
47
Publication 1794-IN096D-EN-P - June 2018
14
15
A
31
32
33
B
-V
Common
48
49
50
51
C
Voltage
Out +V
1794-TB3 shown
9

Hide quick links: