Table 47-1
Evaporator Fan Performance 6, 7 Ton YC 074, YC 086C
.10
Tons
Model No.
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor &
Field Supplied Low Static Drive
2000 680 0.45 738 0.50 794 0.55 846 0.59 894 0.63 947 0.67 1003 0.70 1055 0.72
2250 751 0.63 804 0.69 853 0.74 903 0.80 949 0.84 992 0.88 1037 0.92 1086 0.97 1135 1.00 1181 1.03
YCH074C-H
2500 824 0.84 872 0.91 917 0.97 961 1.03 1006 1.09 1047 1.14 1086 1.19 1126 1.24 1167 1.28 1212 1.33
2750 899 1.11 940 1.18 984 1.25 1023 1.32 1064 1.39 1105 1.45 1142 1.51 1178 1.56 1214 1.61 1250 1.66
3000 974 1.42 1010 1.50 1051 1.58 1089 1.65 1125 1.73 1162 1.80 1200 1.88 1235 1.94 1268 1.99
6
1 HP Standard Motor & Field Supplied
Low Static Drive
2000 615 0.37 663 0.41 710 0.45 756 0.49 799 0.52 843 0.55 884 0.58 924 0.60 965 0.62 1006 0.63
YCD074C-L,H
2250 681 0.52 723 0.56 766 0.61 807 0.65 848 0.69 886 0.73 925 0.76 964 0.79 1000 0.82 1035 0.84 1126 0.90 1209 0.92
YCH074C-L
2500 748 0.69 785 0.74 824 0.79 862 0.84 899 0.89 936 0.93 971 0.98 1005 1.02 1041 1.06 1075 1.09 1154 1.16 1237 1.22
2750 816 0.91 849 0.96 884 1.02 920 1.08 954 1.13 988 1.18 1021 1.23 1053 1.28 1084 1.32 1116 1.37 1195 1.46 1266 1.54
3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80
1 HP Standard Motor &
Field Supplied Low Static Drive
2000 680 0.45 738 0.50 794 0.55 846 0.59 894 0.63 947 0.67 1003 0.70 1055 0.72
2250 751 0.63 804 0.69 853 0.74 903 0.80 949 0.84 992 0.88 1037 0.92 1086 0.97 1135 1.00 1181 1.03
YCH086C-H
2500 824 0.84 872 0.91 917 0.97 961 1.03 1006 1.09 1047 1.14 1086 1.19 1126 1.24 1167 1.28 1212 1.33
2750 899 1.11 940 1.18 984 1.25 1023 1.32 1064 1.39 1105 1.45 1142 1.51 1178 1.56 1214 1.61 1250 1.66
3000 974 1.42 1010 1.50 1051 1.58 1089 1.65 1125 1.73 1162 1.80 1200 1.88 1235 1.94 1268 1.99
7
1 HP Standard Motor & Field Supplied
Low Static Drive
2000 615 0.37 663 0.41 710 0.45 756 0.49 799 0.52 843 0.55 884 0.58 924 0.60 965 0.62 1006 0.63
YCD086C-L,H
2250 681 0.52 723 0.56 766 0.61 807 0.65 848 0.69 886 0.73 925 0.76 964 0.79 1000 0.82 1035 0.84 1126 0.90 1209 0.92
YCH086C-L
2500 748 0.69 785 0.74 824 0.79 862 0.84 899 0.89 936 0.93 971 0.98 1005 1.02 1041 1.06 1075 1.09 1154 1.16 1237 1.22
2750 816 0.91 849 0.96 884 1.02 920 1.08 954 1.13 988 1.18 1021 1.23 1053 1.28 1084 1.32 1116 1.37 1195 1.46 1266 1.54
3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80
Table 47-2
Evaporator Fan Performance 7½ Ton Dual Compressor YC 091D
.10
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied
Low Static Drive
2400 795 0.75 845 0.81 891 0.87 938 0.94 983 0.99 1025 1.03 1065 1.08 1107 1.12 1153 1.17 1200 1.21
2700 884 1.05 926 1.12 970 1.19 1010 1.26 1052 1.33 1093 1.39 1131 1.44 1167 1.49 1203 1.54 1241 1.59
YCH091D-H
3000 974 1.42 1010 1.50 1051 1.58 1089 1.65 1125 1.73 1162 1.80 1200 1.88 1235 1.94 1268 1.99
3300 1064 1.87 1097 1.95 1133 2.04 1170 2.13 1203 2.21 1235 2.29 1270 2.38
3600 1154 2.41 1185 2.50 1216 2.59 1250 2.69
2400 721 0.62 760 0.66 801 0.71 840 0.76 879 0.80 916 0.85 952 0.89 988 0.92 1025 0.96 1058 0.99 1142 1.05 1226 1.10
YCD091D-L,H
2700 802 0.86 836 0.92 872 0.97 908 1.03 943 1.08 977 1.13 1011 1.17 1043 1.22 1075 1.27 1108 1.31 1186 1.40 1259 1.47
YCH091D-L
3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80
3300 966 1.54 994 1.60 1022 1.67 1051 1.73 1081 1.80 1111 1.87 1139 1.93 1167 1.99 1195 2.05 1223 2.11 1289 2.26
3600 1048 1.98 1075 2.06 1101 2.12 1126 2.20 1153 2.27 1181 2.34 1208 2.42 1234 2.49
Data includes pressure drop due to filters and wet coil.
Fan motor heat (MBH) = 3.53 x Fan Bhp.
Trane's factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
1. Field supplied Browning fan sheave AL74 and Belt A48 required.
2. Field supplied Browning motor sheave IVL34 and Belt A48 required.
Performance
Data
External Static Pressure (Inches of Water)
.20
.30
.40
1 HP Standard Motor & Sheaves
1
2 HP Oversize Motor & Sheaves
1
1 HP Standard Motor & Sheaves
1
1 HP Standard Motor & Sheaves
1
1 HP Standard Motor & Sheaves
External Static Pressure (Inches of Water)
.20
.30
.40
2
1 HP Standard Motor
2 HP Oversize Motor & Sheaves
6, 7, 7½ Ton
High Efficiency
.50
.60
.70
.80
2 HP Oversize Motor & Sheaves
2 HP Oversize Motor & Sheaves
.50
.60
.70
.80
2 HP Standard Motor & Sheaves
Indicates both downflow and horizontal units.
47
.90
1.00
1.25
1.50
2 HP Oversize Motor & Sheaves
.90
1.00
1.25
1.50