Performance Data - 20, , , , , 25 Ton Standard Efficiency - Trane Voyager Manual

Product
Table of Contents

Advertisement

Table 30-1
Gross Cooling Capacities (MBH) 20 Ton Three Phase YC 240B3, B4, BW
85
Enter.
Dry
CFM
Bulb
61
67
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
228.4 184.9 251.1 137.8 265.2
80
228.4 221.0 251.1 174.7 265.2 130.4 217.0 213.3 242.3 171.2 260.3 128.0 203.2 202.3 230.5 167.1 253.3 124.8 190.1 190.1 215.7 162.7 244.2 122.1
7200
85
229.9 229.9 251.1 212.0 265.2 174.2 224.5 224.5 242.3 209.5 260.3 172.5 216.6 216.6 230.5 206.9 253.3 169.1 204.1 204.1 215.7 203.7 244.2 166.9
90
238.6 238.6 251.1 244.9 265.2 200.7 235.9 235.9 242.3 239.0 260.3 199.8 220.5 220.5 230.5 229.8 253.3 196.9 218.6 218.6 217.3 217.3 244.2 195.3
75
231.9 193.2 254.9 144.0 269.3
80
231.9 231.0 254.9 182.5 269.3 136.2 222.9 222.9 246.0 178.8 264.2 133.7 211.4 211.4 234.0 174.6 257.1 130.4 198.7 198.7 218.9 170.0 247.9 127.6
8000
85
240.2 240.2 254.9 221.5 269.3 182.0 234.6 234.6 246.0 218.9 264.2 180.2 226.3 226.3 234.0 216.2 257.1 176.7 213.3 213.3 218.9 212.9 247.9 174.4
90
249.3 249.3 255.9 255.9 269.3 209.8 246.5 246.5 249.7 249.7 264.2 208.8 230.4 230.4 240.1 240.1 257.1 205.7 228.5 228.5 227.0 227.0 247.9 204.1
75
235.1 199.9 258.5 149.1 273.0
80
239.0 239.0 258.5 188.9 273.0 141.0 230.7 230.7 249.4 185.1 267.9 138.4 218.8 218.8 237.3 180.7 260.7 134.9 205.6 205.6 222.0 176.0 251.4 132.1
8800
85
248.6 248.6 258.5 229.3 273.0 188.4 242.8 242.8 249.4 226.6 267.9 186.5 234.2 234.2 237.3 223.8 260.7 182.8 220.7 220.7 222.0 220.3 251.4 180.5
90
258.0 258.0 264.9 264.9 273.0 217.1 255.1 255.1 258.4 258.4 267.9 216.1 238.4 238.4 248.5 248.5 260.7 212.9 236.5 236.5 235.0 235.0 251.4 211.2
75
238.6 209.8 262.3 156.4 277.1 104.1 226.7 204.8 253.1 151.2 271.9 100.4 212.3 197.1 240.8 144.1 264.6 96.1 195.4 189.0 225.3 137.1 255.1
80
250.8 250.8 262.3 198.2 277.1 148.0 242.1 242.1 253.1 194.2 271.9 145.2 229.6 229.6 240.8 189.6 264.6 141.6 215.7 215.7 225.3 184.6 255.1 138.6
9600
85
260.9 260.9 262.3 240.6 277.1 197.7 254.8 254.8 253.1 237.8 271.9 195.7 245.8 245.8 240.8 234.8 264.6 191.8 231.6 231.6 231.2 231.2 255.1 189.4
90
270.7 270.7 277.9 277.9 277.1 227.8 267.7 267.7 271.2 271.2 271.9 226.7 250.2 250.2 260.7 260.7 264.6 223.4 248.1 248.1 246.6 246.6 255.1 221.7
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table 30-2
Gross Cooling Capacities (MBH) 25 Ton Three Phase YC 300B3, B4, BW
85
Enter.
Dry
CFM
Bulb
61
67
Airflow
(F)
MBH SHC MBH SHC MBH
75
272.0 226.0 299.0 186.0 318.0 117.0 254.0 216.0 285.0 179.0 307.0 110.0 234.0 206.0 267.0 170.0 294.0 103.0 214.0 195.0 246.0 161.0 277.0 95.9
9000
80
275.0 270.0 300.0 214.0 319.0 158.0 257.0 257.0 286.0 208.0 309.0 153.0 241.0 241.0 268.0 199.0 295.0 145.0 224.0 224.0 247.0 189.0 277.0 137.0
85
288.0 288.0 301.0 255.0 322.0 194.0 274.0 274.0 287.0 250.0 310.0 191.0 258.0 258.0 269.0 242.0 296.0 186.0 241.0 241.0 248.0 231.0 278.0 179.0
90
301.0 301.0 304.0 295.0 324.0 230.0 289.0 289.0 289.0 289.0 312.0 229.0 275.0 275.0 275.0 275.0 297.0 226.0 259.0 259.0 259.0 259.0 279.0 220.0
75
277.0 238.0 303.0 196.0 320.0 119.0 259.0 228.0 289.0 189.0 310.0 113.0 239.0 218.0 272.0 180.0 296.0 106.0 218.0 207.0 250.0 171.0 280.0 96.8
10000
80
281.0 281.0 304.0 222.0 322.0 161.0 266.0 266.0 290.0 217.0 311.0 157.0 249.0 249.0 272.0 209.0 298.0 151.0 231.0 231.0 251.0 199.0 280.0 143.0
85
295.0 295.0 306.0 266.0 325.0 199.0 283.0 283.0 291.0 263.0 314.0 197.0 267.0 267.0 274.0 256.0 299.0 193.0 250.0 250.0 254.0 246.0 281.0 188.0
90
308.0 308.0 310.0 309.0 328.0 238.0 297.0 297.0 297.0 297.0 316.0 238.0 283.0 283.0 283.0 283.0 301.0 236.0 267.0 267.0 267.0 267.0 283.0 232.0
75
279.0 244.0 304.0 201.0 321.0 120.0 261.0 234.0 290.0 194.0 311.0 113.0 241.0 224.0 273.0 185.0 297.0 107.0 221.0 213.0 252.0 176.0 281.0 99.4
80
284.0 284.0 306.0 226.0 323.0 163.0 270.0 270.0 292.0 222.0 312.0 159.0 253.0 253.0 274.0 214.0 299.0 153.0 235.0 235.0 253.0 204.0 282.0 146.0
10500
85
298.0 298.0 308.0 271.0 326.0 201.0 286.0 286.0 293.0 269.0 315.0 200.0 271.0 271.0 276.0 263.0 301.0 197.0 254.0 254.0 257.0 254.0 283.0 191.0
90
311.0 311.0 311.0 311.0 329.0 241.0 300.0 300.0 300.0 300.0 317.0 242.0 287.0 287.0 286.0 286.0 302.0 241.0 271.0 271.0 271.0 271.0 284.0 237.0
75
281.0 249.0 305.0 205.0 322.0 121.0 263.0 240.0 292.0 198.0 312.0 114.0 243.0 229.0 275.0 190.0 299.0 108.0 223.0 219.0 254.0 181.0 281.0 104.0
80
287.0 287.0 307.0 230.0 324.0 164.0 273.0 273.0 293.0 226.0 314.0 160.0 256.0 256.0 276.0 219.0 300.0 155.0 238.0 238.0 255.0 210.0 283.0 148.0
11000
85
301.0 301.0 309.0 276.0 327.0 204.0 289.0 289.0 295.0 275.0 316.0 203.0 275.0 275.0 278.0 269.0 302.0 200.0 258.0 258.0 257.0 257.0 284.0 195.0
90
314.0 314.0 314.0 314.0 330.0 244.0 303.0 303.0 303.0 303.0 319.0 246.0 290.0 290.0 289.0 289.0 304.0 245.0 274.0 274.0 274.0 274.0 286.0 243.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Indicates both downflow and horizontal units.
Performance
Data
Ambient Temperature
95
Entering Wet Bulb
73
61
67
73
91.7 217.0 180.4 242.3 133.2 260.3
88.5 203.2 173.7 230.5 127.0 253.3
95.9 220.3 188.5 246.0 139.2 264.2
92.5 206.3 181.5 234.0 132.7 257.1
99.2 223.4 195.1 249.4 144.1 267.9
95.7 209.2 187.9 237.3 137.3 260.7
Ambient Temperature
95
Entering Wet Bulb
73
61
67
73
SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
30
20, , , , , 25 Ton
Standard Efficiency
105
61
67
73
61
84.7 187.1 166.6 215.7 120.8 244.2
88.5 189.9 174.1 218.9 126.2 247.9
91.6 192.6 180.2 222.0 130.6 251.4
105
61
67
73
61
115
67
73
81.4
85.1
88.0
92.4
115
67
73
MBH SHC
MBH SHC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents