Table 42-1
Evaporator Fan Performance
.10
.20
.30
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor & Field Supplied Low Static Drive (1)
3200
— 759 1.21 790 1.31 818 1.40 844 1.50 870
3600
807 1.53 838 1.65 867 1.77 893 1.88 918 1.99 942
4000
891 2.06 918 2.20 946 2.34 971 2.47 994 2.59 1017 2.71 1038 2.83 1059 2.95 1080 3.07 1100 3.19 1119 3.31 1138 3.44 1157 3.56
4400
975 2.72 999 2.86 1025 3.02 1049 3.17 1071 3.31 1092 3.44 1113 3.57 1133 3.70 1152 3.83 1171 3.97 1190 4.10 1208 4.23 1226 4.37
4800
1059 3.51 1082 3.65 1105 3.82 1128 3.99 1149 4.16 1170 4.30 1189 4.45 1208 4.59 1226 4.73 1244 4.87 1262 5.02 1279 5.16 1296 5.31
For Standard Evaporator Fan Speed (RPM), reference Table 53-1.
For Oversize Evaporator Fan Speed (RPM), reference Table 53-3.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to filters and wet coils.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be Necessary.
2. 5 HP Oversize Motor with Field Supplied Fan Sheave BK120 Required.
Field Supplied Belt may be Necessary.
Table 42-2
Evaporator Fan Performance
.10
.20
.30
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor &
Field Supplied Low Static Drive (1)
4000
604 1.11 647 1.27 687 1.44 723 1.60 756 1.75 787
4500
669 1.53 708 1.71 745 1.90 780 2.09 811 2.27 841
5000
735 2.06 770 2.25 804 2.46 837 2.67 868 2.89 897
5500
802 2.70 834 2.90 865 3.13 896 3.36 926 3.60 954
6000
869 3.46 898 3.68 928 3.92 956 4.17 984 4.42 1011 4.68 1037 4.94 1061 5.18 1084 5.40 1106 5.63
For Standard Evaporator Fan Speed (RPM), reference Table 53-1.
For Oversize Evaporator Fan Speed (RPM), reference Table 53-3.
Data includes pressure drop due to filters and wet coils.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be Necessary.
2 3 HP Standard Motor with Field Supplied Motor Sheave 1VP44 Required. Field Supplied Belt may be Necessary.
3. 5 HP Oversize Motor with Field Supplied Motor Sheave 1VP50 Required. Field Supplied Belt may be Necessary.
Performance
Data
10 Ton
YCH120C
External Static Pressure (Inches of Water)
.40
.50
.60
.70
1.59
894 1.69 918 1.79 941 1.89 964 1.98 986 2.08 1007 2.17 1029 2.27
2.10
965 2.21 987 2.32 1009 2.43 1030 2.54 1051 2.65 1071 2.75 1091 2.86
Table 42-1 (Continued)
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3200 1049 2.37 1070 2.48 1090 2.59 1110 2.70 1130 2.81 1149 2.93 1170 3.06
3600 1111 2.96 1130 3.07 1149 3.18 1167 3.29 1186 3.41 1204 3.53 1222 3.65
4000 1175 3.68 1194 3.80 1211 3.92 1229 4.03 1246 4.15 1264 4.27 1281 4.39
4400 1243 4.51 1260 4.64 1277 4.77 1294 4.91 1311 5.04 1327 5.17 1343 5.29
4800 1313 5.46 1329 5.60
12 1/2 Ton
External Static Pressure (Inches of Water)
.40
.50
.60
1.90
818 2.06 848 2.23 877 2.40 906 2.58 933 2.77 960 2.96 987 3.15
2.44
869 2.60 896 2.77 923 2.96 950 3.15 977 3.34 1002 3.54 1027 3.75
3.08
923 3.27 949 3.45 974 3.64 999 3.83 1023 4.03 1048 4.24 1072 4.46
3.83
980 4.04 1004 4.25 1028 4.46 1051 4.66 1074 4.87 1096 5.07 1119 5.30
5 HP Oversize Motor & Drive
Table 42-2 (Continued)
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 1013 3.34 1038 3.54 1063 3.74 1087 3.95 1111 4.10 1134 4.37 1156 4.58
4500 1052 3.96 1076 4.17 1100 4.38 1123 4.60 1146 4.82 1168 5.05 1190 5.28
5000 1095 4.68 1118 4.90 1140 5.13 1163 5.36 1184 5.60
5500 1141 5.53
6000
42
10, , , , , 12½ Ton
Standard Efficiency
.80
.90
1.00
5 HP Oversize Motor & Drive
Trane's factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or premature motor failure. Our
product's warranty will not be affected.
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
3 HP Standard Motor and Drive
5 HP Oversize Motor & Drive
YCD150C
.70
.80
.90
1.00
3 HP Standard Motor & Drive
Trane's factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or premature motor failure. Our
product's warranty will not be affected.
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
(2)
5 HP Oversize Motor & Drive
1.00
1.20
1.30
3 HP Standard Motor and Drive
1.80
1.90
2.00
(2)
1.10
1.20
1.30
(2)
1.80
1.90
2.00
(3)

Hide quick links:

Advertisement

Table of Contents
loading