KLAY-INSTRUMENTS 2000-SAN Series Instruction Manual page 20

Intelligent pressure- and level transmitters
Hide thumbs Also See for 2000-SAN Series:
Table of Contents

Advertisement

Instruction Manual Series 2000 HART
As standard the transmitter is delivered without Linearization (= 0). However, for a
horizontal tank or a tank with a bottom cone, a Linearization can be applied to
achieve the current signal (mA) is equal to the level in the tank. All values must be
programmed in meters.
Linearization horizontal tank (Cylindrical)
Cylindrical horizontal tank
1.
Push [PROG] until "100" is shown on the display.
2.
Push 11 x at [] / SPAN till "111" appears. (Confirm with [PROG])
3.
Push [] once. (Confirm with [PROG])
4.
Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5.
Enter the same height (H2) of the tank in meters. (Confirm with [PROG])
6.
Enter the length (L) of the tank. For a "ball" or cone shaped tank, take the
cylindrical length plus the length of 1 "ball" cone. (Confirm with [PROG])
7.
Enter H3 in meters if the transmitter is installed like in the left picture. Enter
0m when the transmitter is installed like in the right picture.
8.
Enter the percentage of the actual "full" level (for example 80%).
(Confirm with [PROG]).
Linearization horizontal tank (Elliptic)
Cylindrical horizontal tank
1.
Push [PROG] until "100" is shown on the display.
2.
Push 11 x at [] / SPAN till "111" appears. (Confirm with [PROG])
3.
Push [] once. (Confirm with [PROG])
4.
Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5.
Enter the height (H2) of the tank in meters. (Confirm with [PROG])
6.
Enter the length (L) of the tank. For a "ball" or cone shaped tank, take the
cylindrical length plus the length of 1 "ball" cone. (Confirm with [PROG])
7.
Enter H3 in meters if the transmitter is installed like in the left picture. Enter
0m when the transmitter is installed like in the right picture.
8.
Enter the percentage of the actual "full" level (for example 80%).
(Confirm with [PROG]).
Note:
If the height (H) of the tank is 1 meter and the maximum level in the tank is 0,8 meter
the percentage (point 8) must be set at 80%.The calibration at P102 must be adjusted at: 1
meter (if s.g. equals 1).
H/EN/2000-HART/08-2016/24
Cylindrical tank with cone-shaped ends
Cylindrical tank with cone-shaped ends
Klay Instruments B.V.
Page 20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cer-2000 series2000 series2000-hydrobar series

Table of Contents