Table 19: Multiple Point Power Connection Options
Number of electrical circuits
2
2
3
Table 20: Recommended 3-Phase Power Wiring to Ensure Disconnects and Power Blocks Mate with Power Wiring
Wire gauge
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
3/0
4/0
250
300
350
400
500
250
300
350
1. All wire sizes assume separate conduit for each set of parallel conductors.
2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper). Canadian electrical code wire ampacities may vary.
3. All wire sizes assume no voltage drop for short power leads.
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Disconnect designation
DS2
DS1
DS3
DS1
DS3
DS2
DS1
Qty ./pole
Insulation rating (°C)
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
1
75
2
75
2
75
2
75
2
75
2
75
2
75
2
75
3
75
3
75
3
75
Load
Supply and return fan motors plus controls
Balance of unit
Electric heat
Balance of unit
Electric heat
Supply and return fan motors plus controls
Balance of unit
No . of conduits
Conduit (trade size, in .)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
3
3
3
52
Electrical Installation
Location (see Figure 3 on page 4)
Main control panel
Main control panel
Electric heat control panel
Main control panel
Electric heat control panel
Main control panel
Main control panel
For MCA up to (amps)
1/2
35
3/4
50
1
65
1-1/4
85
1-1/4
100
1-1/4
115
1-1/4
130
1-1/2
150
2
175
2
200
2
230
2-1/2
255
2-1/2
285
3
310
3
335
3
380
2
400
2
460
2-1/2
510
2-1/2
570
3
620
3
670
3
760
2-1/2
765
2-1/2
855
3
930
www.DaikinApplied.com