Daikin RoofPak RPS Series Installation And Maintenance Manual page 24

Roof mounted singlezone heating and cooling units with microtech iii unit controllers
Table of Contents

Advertisement

Figure 35: Typical Power Wire Entrance, Curb View (RPS/RFS 015C - 040C Shown, Refer to Submittal Drawings)
Detail A
Post and Rail Mounting
The unit must be level side to side and over the entire length.
Equipment damage can result if the unit is not level.
When mounting by post and rail, run the structural support the
full length of the unit. Locate the structural member at the base
of the unit as shown in
Figure
supported by the structural member.
If resilient material is placed between the unit and the rail, insert
a heavy steel plate between the unit and the resilient material to
distribute the load. Seal cabinet penetrations (electrical, piping,
etc.) properly to protect against moisture and weather.
Table 7: "W" Dimension
(Figure
Unit Dimension
015C-040C
045C-135C
IM 926-3 • ROOFPAK APPLIED SYSTEMS
A
C
D
RA
B
OPNG
A
A
D
2 Typ
4 Typ
0.9 Dia.
K.O.
2.0
4.6
4.8
CAUTION
36, assuring the I-beam is well
36)
"W"
in . (mm)
94 (2388)
99 (2538)
20.0
SA
OPNG
B
See Detail A
Unit length minus 6.4
12.1
5.1
3.4
9.7
Figure 36: Post and Rail Mounting
* Maximum recommended width for structural member is 5" (127 mm)
to allow for adequate space for duct connections and electrical entry
24
Mechanical Installation
6.0
6.8
RPS only
1.5
97.0
76.0
B
7.5
6.0
E
8.0
3.0 Dia.
K.O.
4.3
3.1
2.1
W
www.DaikinApplied.com