Daikin RoofPak RPS Series Installation And Maintenance Manual page 48

Roof mounted singlezone heating and cooling units with microtech iii unit controllers
Table of Contents

Advertisement

Installing Duct Static Pressure Sensor Taps
For all VAV units, field install and connect duct static pressure
taps to the pressure sensors in the unit. Sensor SPS1 is
standard; additional sensor SPS2 is optional. These sensors
are located in the main control panel (see
page
10).
Carefully locate and install the duct static pressure sensing
tap. Improperly locating or installing the sensing tap causes
unsatisfactory operation of the entire variable air volume
system. Below are pressure tap location and installation
recommendations. The installation must comply with local code
requirements
1. Install a tee fitting with a leak-tight removable cap in each
tube near the sensor fitting. This facilitates connecting a
manometer or pressure gauge if testing is required.
2. Use different colored tubing for the duct pressure (HI)
and reference pressure (LO) taps, or tag the tubes.
Daikin recommends 1/4" plastic tubing.
3. Locate the duct pressure (HI) tap near the end of a long
duct to ensure that all terminal box take-offfs along the
run have adequate static pressure.
4. Locate the duct tap in a nonturbulent flow area of the
duct. Keep it several duct diameters away from take-off
points, bends, neckdowns, attenuators, vanes, or other
irregularities.
5. Use a static pressure tip (Dwyer A302 or equivalent) or
the bare end of the plastic tubing for the duct tap. (If the
duct is lined inside, use a static pressure tip device.)
6. Install the duct tap so that it senses only static pressure
(not velocity pressure). If a bare tube end is used,
it must be smooth, square (not cut at an angle) and
perpendicular to the airstream (see
7. Locate the reference pressure (LO) tap somewhere near
the duct pressure tap within the building (see
65). If the reference tap is not connected to the sensor,
unsatisfactory operation will result.
8. Route the tubes between the curb and the supply duct,
and feed them into the unit through the knockout in the
bottom of the control panel (see
tubes to appropriate barbed fittings in the control panel.
(Fittings are sized to accept 1/4" plastic tubing.)
IM 926-3 • ROOFPAK APPLIED SYSTEMS
Control Panel on
Figure
66).
Figure
Figure
65). Connect the
Figure 65: Static Pressure Tubing Entrance Location
Static pressu re
tubing
Figure 66: Pressure Sensing Tubing Installation
Main Control Panel
"HI line"
"LO" line
Remote Sense Point
To Sensor
"HI" input
To Sensor
"LO" Input
Pressure Sensing
Tubing
48
Mechanical Installation
SPS1
Roof
Ductwork
(Remote Location)
Rubber
Grommet
Tubing Extends
thru Approx. 1/8"
www.DaikinApplied.com