3.2.3 Connection cables

The below requirements on the AC/DC cables for connection to the corresponding inverter models should be taken into
account:
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-
5000 / AS-IC01-5000-2/ AS-IC01-6000-2 /
AS-IC01-8000-2 / AS-IC01-10000-2

3.2.4 Micro breakers

In order to ensure safe operation of the inverter and circuits, it is recommender to place micro breakers or fuses on the
DC input end and on the AC output end of the inverter.
Micro breaker specifications:
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-5000 /
AS-IC01-5000-2 / AS-IC01-6000-2
AS-IC01-8000-2 / AS-IC01-10000-2
PD201809 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (4-10 kW) V.2-18 EN
Model
The wiring shall follow local electric codes. Choose proper cables for power input and output lines.
Input and output cables shall be solar cables suitable for outdoor use.
Model
DC side
Min. cross-section
area, mm²
section area, mm²
(length ≤50m)
4
Table 9: Cable specifications
DC input
Recommended breaker
specification
DC1000V, C16A, 2P
DC1000V, C25A, 2P
Table 10: Breaker specifications
AC side
Mini cross-section
Min. cross-
mm² (length ≤50m)
L
(length >50m)
6
AC output
Recommended breaker
specification
AC400V, C16A, 4P
AC400V, C25A, 4P
N/PE
4