RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT GENERAL SAFETY INFORMATION 2 PRECAUTIONS As soon as you open the packaging, check immediately that Never clean the boiler without first disconnecting it from the the contents are all present and undamaged. Contact the mains electricity supply by turning the mains power switch reseller from whom you purchased the product if you and the control panel switch OFF .
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 3 DESCRIPTION OF THE APPLIANCE 4 SAFETY DEVICES RIELLOtech CLIMA TOP and CLIMA COMFORT control panels are de- RIELLOtech CLIMA TOP and CLIMA COMFORT control panels are fit- signed to perform indoor climate control functions.
L T T T A B L E A – the technical data label RIELLO S.p.A. Via Ing. Pilade Riello 7 - 37045 Legnago (VR) - Italia TqelRI100 Cod. : Serial N.° : Mod. : – the code number on the box...
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 8 UNPACKING THE PRODUCT RIELLOtech control panels come in a cardboard box that also contains the following accessories: − Self-tapping fixing screws − instruction manual − outdoor sensor. P A N N E L C O N...
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 10 ASSEMBLY RIELLOtech control panels can be installed either on the top of the boiler or on one of its side panels. Before commencing installation, check the arrangement of the holes on the top panel or side panel of the boiler. SIDE panels TOP of boiler TOP of boiler...
Page 10
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT HORIZONTAL installation o i l e o i l e to sensor socket to sensor socket in boiler in boiler A dedicated kit is available for wall mounting. Refer to the instructions provided with the kit for details on installation. Take care when unwinding thermostat cables.
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 11 ACCESSING INTERNAL COMPONENTS 12 ELECTRICAL CONNECTIONS Only personnel from ’s Technical Assistance Service or pro- All electrical connections must be made by a legally qualified fessionally qualified heating engineers are allowed to access heating engineer according to the following instructions.
Page 12
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOtech CLIMA TOP (used with a single stage or two-stage burner) STORAGE CYLINDER temp. sensor OUTDOOR temp. sensor 12 V room unit power supply 10V input / BOILER Room thermostat ROOM UNIT 1 temp.
Page 13
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOtech CLIMA TOP (used with a modulating burner) STORAGE CYLINDER temp. sensor OUTDOOR temp. sensor 12 V room unit power supply 10V input / BOILER Room thermostat ROOM UNIT 1 temp.
Page 14
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOtech CLIMA COMFORT (used with a single stage or two-stage burner) STORAGE CYLINDER temp. sensor 12 V room unit power supply OUTDOOR temp. sensor 0-10V input / Room thermostat BOILER ROOM UNIT 1 temp.
Page 15
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOtech CLIMA COMFORT (using a three position modulating burner) STORAGE CYLINDER temp. sensor 12 V room unit power supply 0-10V input / Room thermostat BOILER ROOM UNIT 1 temp.
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 13 LOCATION OF SENSORS To measure effective water return temperature and to control the temperature stabilisation function, the socket for the return temperature sensor must be positioned at a distance of 3 to 5 Correct positioning of the temperature sensors is essential to times the diameter of the water return pipe upstream from any proper indoor climate control.
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 14 CONNECTING THE OUTDOOR TEMPERATURE SENSOR The correct positioning of the outdoor sensor is of fundamental importance for proper climate control operation. The sensor must be installed outside the building to be heated, at approx.
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 15 WIRING DIAGRAMS Functional electrical diagram for RIELLOtech CLIMA TOP panel SCH2 X50-1/5 SCH1 Fuse (6.3 A-T) Main switch SCH1 Main control board SCH2 Display and control card Safety thermostat (110°C +0/-6) Electrical power indicator Safety thermostat trip indicator...
Page 19
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Typical component connection diagram for system with RIELLOtech CLIMA TOP panel and two stage burner U1 U1 0-10V signal to modulating burner SCH2 SC SB SCH1 L1 N PE T2 S3 B4 B5 T6 T7 T8 Components to be provided by the installer...
Page 20
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Typical component connection diagram for system with RIELLOtech CLIMA TOP panel and modulating burner U1 U1 0-10V signal to modulating burner SC SB SCH2 SCH1 common increase burner reduce heat output burner heat...
Page 21
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Functional electrical diagram for RIELLOtech CLIMA COMFORT panel SCH2 X30-1/5 Fuse (6.3 A-T) Main switch Burner SCH1 Main control board reset SCH2 Display and control card Safety thermostat (110°C +0/-6) N PE Electrical power indicator 230 V~50 Hz...
Page 22
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Typical component connection diagram for system with RIELLOtech CLIMA COMFORT panel and two stage burner SCH2 X30-1/5 SC SB SCH1 T1 T2 S3 T6 T7 T8 Components to be provided by the installer Room thermostat Boiler temperature sensor Boiler sensor...
Page 23
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Typical component connection diagram for system with RIELLOtech CLIMA COMFORT panel and modulating burner SCH2 X30-1/5 SC SB SCH1 common increase burner reduce heat output burner heat output L1 N PE T1 T2 S3 power supply REDUCE heat...
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 16 SYSTEM LAYOUT 9 10 14 13 Electrical power indicator (green). Lights to show that the system is receiving electrical power Safety thermostat trip indicator (red). Lights if temperature inside the boiler exceeds 110°C Burner lockout indicator (red).
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 17 DESCRIPTION OF FUNCTIONS DISPLAY DHW mode: ON or OFF Central heating modes: AUTOMATIC Continuous COMFORT Continuous REDUCED Frost protection. The display shows the C symbol Small numeric display. time Message area Daily heating program indicator Large numeric display: current value...
Page 26
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT MAIN SCREEN Boiler temperature A1 DHW mode: ON or OFF . Press the DHW button (5) to switch DHW on or off (as shown by the line under the symbol) B1 Central heating modes.
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 18 MODE SELECTION − All protection functions are active − Limitation of cooling on the basis of outdoor temperature Press the central heating mode button (5) to select the various −...
Page 28
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Information Manual mode Press the information button (6) to display: When you select manual mode, the "h" symbol appears and − Errors or maintenance codes (see the section "Error/ relays are energised/de-energised not according to any heating maintenance codes”) program but according to a default manual setting that can be...
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT The following parameters refer EXCLUSIVELY to the end user level. Proceed as follows to access the user level you require: − Go to the main screen. If not displayed, press E one Reset ? or more times −...
Page 30
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Example: setting the current time The new time setting is saved and the display starts to flash. At − Go to the main screen and press "K". this stage you can continue programming or press the central −...
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 20 ERROR/MAINTENANCE CODES Error code Description 2 clock time masters (LPB) When the alarm symbol n warns of an error, press the button (6) Clock time master without backup (LPB) to display a description.
Page 32
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Special operation code Error code Description Operation Collector pump Q5 missing Description code Collector pump Q16 missing Manual operation Collector sensor B6 missing SLT test Solar DHW sensor B31 missing Chimney sweep function Solar integration missing Simulation outside temperature...
RIELLOtech CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT 21 LIST OF PARAMETERS User legend: Legend: IMPORTANT! The following parameter descriptions E: End user QAA75../78 only may differ from those on the controller for rea- O: OEM (**) RIELLOtech CLIMA COMFORT only...
Page 34
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 2nd phase on 24:00 00:00 24:00 hh:mm 2nd phase off 24:00 00:00 24:00 hh:mm 3rd phase on 24:00 00:00 24:00 hh:mm 3rd phase off...
Page 35
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Heating circuit 1 Operating mode Automatically Protection ¦ Automatic ¦ Reduced ¦ Comfort Comfort setpoint 20,0 OL 712 OL 716 °C Reduced setpoint OL 714...
Page 36
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Optg mode changeover Protection mode None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic Cooling circuit 1 Operating mode 901(**) Automatically Off ¦...
Page 37
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 1050 Room influence - - - / 1 - - - / 1060 Room temp limitation °C 1070 Boost heating - - - / 0 °C Down to reduced set...
Page 38
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 1342(**) Flow temp setpoint room stat OL 1340 OL 1341 °C 1344(**) Swi-on ratio room stat - - - - - - / 1 1350 Room influence...
Page 39
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 1641 Legionella funct periodically Days Legionella funct weekday 1642 Monday Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦ Saturday ¦ Sunday - - - / 1644...
Page 40
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Swimming pool circuit 1959(**) Flow temp setpoint °C Frost prot plant pool pump 1960(**) Off ¦ On DHW charging priority 1974(**) No ¦...
Page 41
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 2240 Switching differential boiler °C 2241 Burner running time min 2250 Pump overrun time Prot boil startup consumers 2260 Off ¦...
Page 42
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 3590 Temp differential min - - - / 0 °C Supplementary source 3690(**) Setpoint incr main source °C 3691(**) Output limit main source - - - - - - / 1...
Page 43
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 3881 Antifreeze concentration 3884 Pump capacity - - - 1500 Pulse count yield None ¦ With input H1 ¦ With input H3 ¦ With input H31 Module 1 ¦ 3886 (**) None With input H31 Module 2 ¦...
Page 44
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 4726(**) Max st tank temp cool mode - - - / 10 °C 4728(**) Rel temp diff buffer/HC Stratification protection 4739(**) Off ¦...
Page 45
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level With buffer 5090 No ¦ Yes With prim contr/system pump 5092 No ¦ Yes With solar integration 5093 No ¦ Yes 5101 Pump speed min 5102...
Page 46
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Configuration Heating circuit 1 5710 Off ¦ On Cooling circuit 1 5711(**) Off ¦ 4-pipe system ¦ 2-pipe system Use of mixing valve 1 5712(**) Heating and cooling...
Page 47
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Relay output QX3 None ¦ Circulation pump Q4 ¦ El imm heater DHW K6 ¦ Collector pump Q5 ¦ Cons circ pump CC1 Q15 ¦ Boiler pump Q1 ¦ Bypass pump Q12 ¦...
Page 48
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Function input H1 Optg mode changeover HCs +DHW ¦ Optg mode changeover DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg mode changeover HC2 ¦...
Page 49
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 6100 Readjustm outside sensor -3,0 °C Sensor type flue gas temp 6101 NTC ¦ Pt 1000 6102 Readjustm flue gas sensor °C 6110 Time constant building...
Page 50
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 6215 Check no. storage tank 199999 6217 Check no. heating circuits 199999 6220 Software version 99,9 6222 Device hours run 65535 6270(**) Excess heat discharge temp...
Page 51
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 6805 Error code 3 6806 History 4 6807 Error code 4 6808 History 5 6809 Error code 5 6810 History 6 6811 Error code 6...
Page 52
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Relay output QX23 module 1 7303(**) OL 7301 Sensor input BX21 module 1 None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return sensor B7 ¦ DHW circulation sensor B39 ¦...
Page 53
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Voltage out GX21 module 1 7341(**) 5 Volt 5 Volt ¦ 12 Volt Funct input EX21 module 1 7342(**) None ¦...
Page 54
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Function input H2 module 2 None ¦ Optg mode change HCs+DHW ¦ Optg mode changeover DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg mode changeover HC2 ¦...
Page 55
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Sign logic out UX21 module2 7424(**) Standard Standard ¦ Inverted Signal output UX21 module 2 7425(**) 0,,10V 0..10V ¦ PWM 7429(**) Temp val 10V UX21 module2 °C...
Page 56
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level Function input H21 module 3 None ¦ Optg mode change HCs+DHW ¦ Optg mode changeover DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg mode changeover HC2 ¦...
Page 57
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 7730 Outside temp B9 -50,0 °C 7732 Flow temp B1 °C 7734(***) Flow temp B12 °C 7750 DHW temp B3 °C 7760 Boiler temp B2...
Page 58
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 7847(**) Input signal H21 module 2 65535 [Output signal H21 module 2] 7847(**) None None ¦ Closed (ooo), Open (- - -) ¦ Pulse ¦ Frequency Hz ¦ Voltage V 7848(**) Input signal H22 module 2 65535...
Page 59
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 8308(***) Boiler pump speed 8310 Boiler temp 140,0 °C 8311 Boiler setpoint 140,0 °C 8312 Boiler switching point °C 8314 Boiler return temp 140,0...
Page 60
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 8741 Room setpoint 1 35,0 °C 8742 Room temp 1 model 50,0 °C 8743 Flow temp 1 140,0 °C 8744 Flow temp setpoint 1 140,0...
Page 61
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT Operat- User Function Default value Unit ing line level 8930 Primary controller temp 140,0 °C 8931 Primary controller setpoint 140,0 °C 8950 Common flow temp 140,0 °C 8951 Common flow temp setpoint 140,0 °C...
Page 62
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT...
Page 63
RIELLOTECH CLIMA TOP - CLIMA COMFORT RIELLOTECH CLIMA TOP - CLIMA COMFORT...
Page 64