APPENDIX J - TROUBLESHOOTING TABLE

LOCKOUT CODES
Error no. Error
0
E2PROM_READ_ERROR
1
IGNIT_ERROR
2
GV_RELAY_ERROR
3
SAFETY_RELAY_ERROR
4
BLOCKING_TOO_LONG
5
FAN_ERROR_NOT_RUNNING
6
FAN_ERROR_TOO_SLOW
7
FAN_ERROR_TOO_FAST
8
RAM_ERROR
9
WRONG_EEPROM_SIGNATURE
10
E2PROM_ERROR
11
STATE_ERROR
12
ROM_ERROR
13
APS_NOT_OPEN
14
APS_NOT_CLOSED
Description
Internal software error
Three unsuccessful ignition
attempts in a row
Failure detected in the GV
(Gas Valve) relay
Failure detected in the Safe-
ty relay
Control had a blocking error
for more than 20 hours
Fan is not running for more
than 60 seconds
Fan runs too slow for more
than 60 seconds
Fan runs too fast for more
than 60 seconds
Internal software error
Contents of E2PROM is not up
to date
Wrong safety parameters in
E2PROM
Internal software error
Internal software error
Air pressure switch not
working
Air pressure switch not
working
44
44
Checks
a- Check gas supply pres-
sure;
b- Check ignition spark;
c- Correct amount of air;
d-Check for120VAC at the gas
valve.
a- Check the integrity of the
wire connections between
gas valve and control board.
Press RESET button to
display the Blocking error
description
a- Check for 120 Vac power
connection of the fan.
b- Check PWM connection of
the fan.
Solutions
Replace the power control
board
a- If the gas supply pres-
sure is incorrect, it must
be adjusted to the correct
pressure;
b- If spark is not present
check for correct ignition
electrode position;
c- If the combustion air
pressure is incorrect, inspect
the vent system and elimi-
nate any obstructions;
d- If the voltage to the gas
valve is not 120Vac the pow-
er control board must be
replaced.
a- If wires are damaged,
replace them
b- If wires are ok, replace
the gas
valve or the power control
board.
Replace the power control
board
Remove the cause of the
Blocking
error
a- If no 120 VAC voltage is
present, replace the power
control board;
b- If no PWM signal is pres-
ent, replace power control
board;
c- Replace the fan.
Replace the power control
board
Replace the power control
board
Replace the power control
board
Replace the power control
board
Replace the power control
board