APPENDIX G - HEAD AVAILABLE FOR THE SYSTEM

HEAD AVAILABLE (NO GLYCOL)
Array
∆T = 36°F
AR 3000
2ft
AR 4000
2ft
HEAD AVAILABLE (65% GLYCOL)
∆T = 36°F
Array
AR 3000
0ft
AR 4000
0ft
Array
Boiler
Combined
Model
Quantity
Max GPM
1
150
2
300
AR 3000
3
450
4
600
1
400
2
800
AR 4000
3
1200
4
1600
Notes:
Max equivalent length of pipes must account for all pipes, valves,
fittings and a recommended strainer at boiler inlet.
Multiple boilers to be piped in reverse return layout.
∆T = 45°F
12ft
12ft
∆T = 45°F
9,5ft
9,5ft
Common
Max Equiva-
Pipe Size
lent Length
(Inch)
of Pipe (ft)
4
150
6
300
6
150
8
330
6
180
8
180
10
265
10
160
41