Concentric balanced flue, horizontal C13x, C83x and B33
and flue on an external wall C53x (examples)
3a
Horizontal balanced flue routed through pitched roof
5
2
C13x
without internal pipe
18
6
21 Flue pipe DN110
500 mm
1000 mm
2000 mm
22
Bend 87° DN 100
23 Spacer
24 Duct cover
25 Air inlet pipe Ø 110 mm
26 Air pipe Ø 160 mm
52
28. Technical information
5
4
3a
5
Flue routed along external wall
3a
2
1
C53 x
B33
3a
5
C83x
180
Dormer
(on site)
16
17
4
5
5
2
(only where
required)
Recess Ø 120 mm in
chimney side. Install the
flue in the side of the
chimney and ensure it is
airtight.
5
2
Install the horizontal flue with a fall of approx.
1
3° (6 cm/m) towards the boiler. Route the
horizontal air supply with a 3° slope towards
the outside – install the air inlet with a cowl;
permissible wind pressure at the air inlet 90 Pa.
The appliance will not operate with higher wind
pressure. Downstream of the support bend, the
flue Ø 110 mm or the flexible flue DN 110 can
be routed in a duct.
Ventilation air aperture for room sealed operation
according to TRGI 150 cm² or 2 x 75 cm².