P1 Power Pins; P4 Redundancy Link Pins - ABB Symphony Harmony Series Instruction

Input/output system, i/o and auxiliary blocks
Hide thumbs Also See for Symphony Harmony Series:
Table of Contents

Advertisement

I/O Block Connectors
I/O Module (P1, P4, P5)
WBPEEUI240751C0
The following sections provide the pin assignments for I/O
block connectors.
An I/O module has three connection points for external sig-
nals and power: P1 power, P4 redundancy link, and P5 com-
munication. Tables 8-6, 8-7, and
for P1, P4, and P5.
Table 8-6. P1 Power Pins
Pin
Connection
A
1
BLP A (+)
2
BLP B (+)
3
IFP (+)
B
1
BLC A (–)
2
BLC B (–)
3
IFC (–)
Table 8-7. P4 Redundancy Link Pins
Pin
Connection
1
Transmit data A (+)
3
Ground
5
Receive data A (–)
7
Primary/backup
9
Handshake IN
11
Receive data B (+)
13
Transmit data B (–)
8-8
list the pin assignments
Pin
Connection
2
Receive data A (+)
4
Transmit data A (–)
6
Handshake OUT
8
Ground
10
Transmit data B (+)
12
Ground
14
Receive data B (–)
I/O Block Connectors
8 - 13